![Samwontech TEMI2000 Series Communications Manual Download Page 30](http://html1.mh-extra.com/html/samwontech/temi2000-series/temi2000-series_communications-manual_3790127030.webp)
SAMWONTECH
1st Edition of TEMI2000_Series IM : Dec. 15. 2008 Page 28 / 58
█ OPERATION mode & performance setting D-Register
D-Reg.
Symbol
Process method
Setting
Description
RUN
1
Start running PROG/FIX Oper.
HOLD
2
HOLD ON/OFF
STEP
3
Segment STEP
D0101
COM.OPMODE
STOP
4
Stop PROG/FIX Operation
PROG
0
Set PROG Operation MODE
D0104
OP.MODE
FIX
1
Set FIX Operation MODE
STOP
0
Not using Power-Mode
COLD
1
COLD MODE
D0105
PWR.MODE
HOT
2
HOT MODE
☞
To activate PROG operation RUN or FIX operation RUN, TEMI2500 should be in individual corresponding
STOP(PROG STOP/FIX STOP) state. For example, to activate PROG operation RUN from currently operating FIX RUN
state, convert the operation state to PROG STOP (D0104 = 0000, D0101 = 0004) first, then you can activate
PROG operation RUN.