ENGLISH-17
03 OT
H
E
R
S
Main
menu
Sub
menu
Function description
Setting value
Page
Save location
Value
Factory default
5
2
Indoor unit
discharge
temperature
setting/
checking 2)*
Use of discharge
temperature control
0 - No use, 1 - Use
0
01
Indoor unit
Cooling discharge temperature
8~18 °C
15
02
Indoor unit
Heating discharge temperature
30~43 °C
38
03
Indoor unit
3
Fresh duct
indoor unit
discharge
temperature
setting/
checking 2)*
Cooling discharge temperature
13~25 °C
18
01
Fresh duct
indoor unit
Heating discharge temperature
18~30 °C
25
02
Fresh duct
indoor unit
4
AHU Indoor
unit discharge
temperature
setting/
checking 2)*
Use of discharge
temperature control
0 - No use, 1 - Use
0
01
AHU Indoor unit
Cooling discharge temperature
8~25 °C
15
02
AHU Indoor unit
Heating discharge temperature
18~43 °C
38
03
AHU Indoor unit
7
1
View master
setting/
checking
Indoor unit view master setting/
checking
Indoor unit view
master address
(Example : 20 02 1F)
Indoor unit view
master
01~03
None
2
Mode master
indoor unit
setting/
checking
Mode master indoor unit
checking
Indoor unit master
address (Example :
20 02 1F)
none
01~03
None
3
Mode master indoor unit setting
6)*
0-No use, 1-Use,
2-Release 7)*
none
01
None
8
1
Status of automatic air volume setting
1
0
01
Indoor unit
2
Automatic air volume operation
1
0
01
Indoor unit
3
Automatic air volume voltage setting
1
2
01
Indoor unit
0
1
Reset
Factory setting
1
0
None
2
Power master reset 8)*
1
0
None
3
Outdoor units reset
1
0
None
1)* Relative temperature means that the wired remote controller only displays the temperature increase or decrease (± 3)
compared to the reference temperature. Reference temperature is determined by other controller's desired temperature
setting.
(Example : DMS set 24 °C (75 °F)
¤
24 °C (75 °F) is reference temperature. Wired remote controller displays it as '0' )
2)* Only the celsius temperature unit is allowed when this function setting and checking in the service mode.
For the fahrenheit temperature, you need temperature conversion before this function setting and checking
by the celsius temperature unit.
3)* When setting the address/option, you can set the target indoor unit by selecting sub menu 1.