Installing the unit
3 . Using more than two screws, firmly affix the rear cover of the remote controller to the wall, and then connect
communication cables(F3, F4), making sure these cables have reasonable length, to the terminal at the back of the cover .
10 mm or more
10 mm or more
50 mm or more
10 mm or more
Rear cover
Screw hole
Wire (not supplied)
PCB terminal
Front cover
Wired remote
controller
Control kit
❋
❋
Before fixing the rear cover, allow at
least 10 mm space of upper side, left
side, right side, and 50 mm space of
bottom side .
❋
❋
You must fit the screws into the
screw holes .
❋
❋
Do not tighten the screws on the
PCB terminal with excessive force .
4 . Reassemble your wired remote controller .
NOTE
•
Align the controller with the upper groove first, and insert it by turning it downward as shown in the
figure . After assembly, check and confirm that no wires are stuck in the gap between the rear and
front cover .
•
When installing your wired remote controller on the wall, consider the size of the wire hole, and select a wire
with a proper thickness .
•
Wire that is connectable to wired remote controller PCB .
- If you install the wired remote controller by reclaiming, install it according to ring terminal cable specification .
- If you install the wired remote controller by using four pieces of PVC wire, remove the 30 cm of the sheath of
the cable and install it only with the four pieces of wires . (Recommended specification: AWG21)
- The followings are the specs of the compressed ring terminal connectable to your wired remote controller PCB
Stud
Range of Permitted
Wires
Rated Size Stud Size
Basic Size (mm)
AWG
mm
2
mm
2
mm
t
øD
G
E
F
W
L
22 ~ 16
0 .25 ~ 1 .65
1 .5
3
0 .7
3 .8 10 .0 4 .5
6 .5
6 .0 21 .2
❋
❋
Maximum distance of communication cable : 100 m
-
Screws on the PCB terminal must be tightened with less than 0.75 N•m tightening torque. If the tightening
torque is greater, it may damage the screw thread .
CAUTION
8
EHS MONO Kit-EU_IM_05388A-00_EN.indd 8
2015-03-18 오전 11:53:33