Wiring works
Connection of the solar circulation pump for DHW tank
Description
No. of wires
Max. A
Thickness
Supply Scope
Solar pump
2+ground
10 mA
0 .75mm
2
H05RN-F or
H07RN-F
Field supply (230 V~,
Input)
SOLAR PUMP (L)
SOLAR PUMP (N)
Controller
Solar pump
Power
B25
B26
1 . Before the installation, control kit should be turned off .
2 . Using the appropriate equipment to correct position of terminal
block as shown on the diagram .
3 . It is for control kit to inform that the pump is operating .
4 . Solar pump is controlled by installer’s handling . And it send the
signal to control kit depending on solar pump conditions . In
operating mode, signal shall be around 230Vac B/W N&L . In non-
operating mode, signal shall be around 0Vac B/W N&L .
•
Maximun allwable current of each terminal is below
10 mA .
•
Ports number B25, B26 are for input port for detection and
they do not supply power to a solar pump .