Connection of the 3-way valve
Description
No. of wires
Max. A
Thickness
Supply Scope
Diverting type 3way
valve
4
22 mA
> 0 .75 mm
2
, H05RN-F or
H07RN-F
Field supply (230 V~,
Input)
3WAY (L1)
3WAY (L2)
Live (L)
Neutral (N)
B15
B16
B17
B18
Status
L1
L2
3-way diverting valve for water tank
f
f
Diverting typecooling mode, UFH loops will be closed .
f
f
230V AC
1 . Before the installation, control kit should be turned off .
2 . Using the appropriate equipment to correct position of
terminal block as shown on the diagram .
3 . Make sure what type of 3 way V/V you use .
A
(Initial)
OFF
ON
B
ON
OFF
Field Setting Valve (#3071) “0”
Floor heating as default
Field Setting Valve (#3071) “1”
DHW tank as default
FLOOR HEATING
A
DHW TANK
3WAY V/V
Outdoor Unit
FLOOR HEATING
A
DHW TANK
3WAY V/V
Outdoor Unit
FLOOR HEATING
B
DHW TANK
3WAY V/V
Outdoor Unit
FLOOR HEATING
B
DHW TANK
3WAY V/V
Outdoor Unit
Connection of the thermostat
escription
No. of wires
Max. A
Thickness
Supply Scope
Room Thermostat for
weather control
4
22 mA
> 0 .75 mm
2
, H05RN-F or
H07RH-F
Field supply (230 V~,
Input)
N L C1 H1
N L C2 H2
THERMOSTAT02_HEATING (H2)
THERMOSTAT01
THERMOSTAT02
THERMOSTAT02_COOLING (C2)
THERMOSTAT01_HEATING (H1)
THERMOSTAT01_COOLING (C1)
Live (L)
Neutral (N)
B19
B20
B21
B22
B23
B24
1 . Before the installation, control kit should be turned off .
2 . Using the appropriate equipment to correct position of terminal
block as shown on the diagram .
3 . Make sure what type is you use .
- Contact signal must be “ L “ . When you install two thermostats,
thermostat2 is prior to thermostat1 .