![Samsung KXWD Series Installation Manual Download Page 96](http://html1.mh-extra.com/html/samsung/kxwd-series/kxwd-series_installation-manual_4743204096.webp)
ENGLISH-96
Setting outdoor unit option switch and key function
K21 K22
K4 (Number of
press)
KEY operation
Display on segment
SEG 1
SEG2, 3, 4
1 time
Outdoor unit model
1
(a) Capacity
Off, 1, 2
2 times
Target frequency (Compressor 1)
2
120 Hz
1, 2, 0
3 times
Target frequency (Compressor 2)
3
120 Hz
1, 2, 0
4 times
High pressure (MPa)
4
1.52 MPa
1, 5, 2
5 times
Low pressure (MPa)
5
0.43 MPa
0, 4, 3
6 times
Discharge temperature (Compressor 1)
6
87 °C
0, 8, 7
7 times
Discharge temperature (Compressor 2)
7
87 °C
0, 8, 7
8 times
IPM temperature (Compressor 1)
8
87 °C
0, 8, 7
9 times
IPM temperature (Compressor 2)
9
87 °C
0, 8, 7
10 times
CT sensor value (Compressor 1)
A
2 A
0, 2, 0
11 times
CT sensor value (Compressor 2)
B
2 A
0, 2, 0
12 times
Suction temperature
C
-42 °C
-, 4, 2
13 times
COND OUT temperautre
D
-42 °C
-, 4, 2
14 times
Temperature of liquid pipe
E
-42 °C
-, 4, 2
15 times
TOP temperature (Compressor 1)
F
-42 °C
-, 4, 2
16 times
TOP temperature (Compressor 2)
G
-42 °C
-, 4, 2
17 times
Water temperature
H
-42 °C
-, 4, 2
18 times
EVI inlet temperature
I
-42 °C
-, 4, 2
19 times
EVI outlet temperature
J
-42 °C
-, 4, 2
20 times
Main EEV 1 step
K
2000 steps
2, 0, 0
21 times
Main EEV2 step
L
2000 steps
2, 0, 0
22 times
EVI EEV step
M
300 steps
3, 0, 0
23 times
HR EEV step
N
2000 steps
2, 0, 0
24 times
-
O
-
25 times
Current frequency of the compressor 1
P
120 Hz
1, 2, 0
k}tGzG~Tnlvptluki]_TW[^``hTWZUGGG`]
YWX]TW^TYXGGG㝘䟸GXaWYaYW