ENGLISH-29
0
2
INST
ALLING
THE
PRODUC
T
Branch joint
f
Branch joint between outdoor units (C)
Classification
Model name
Specification
MBH
kW
Y-joint for outdoor unit (C)
MXJ-TA3819M
461 and below
135.2 and below
MXJ-TA4422M
478 and over
140.2 and over
f
First branch joint (D)
Make a selection according to outdoor unit capacity.
Classification
Model name
Outdoor unit capacity
MBH
kW
Y-joint (D)
MXJ-YA2512M
Over 51 ~ 136 and below
Over 15.0 ~ 40.0 and below
MXJ-YA2812M
Over 136 ~ 154 and below
Over 40.0 ~ 45.0 and below
MXJ-YA2815M
Over 154 ~ 240 and below
Over 45.0 ~ 70.3 and below
MXJ-YA3419M
Over 240 ~ 336 and below
Over 70.3 ~ 98.4 and below
MXJ-YA4119M
Over 336 ~ 461 and below
Over 98.4 ~ 135.2 and below
MXJ-YA4422M
Over 461
Over 135.2
f
Branch joint (E)
Select a branch joint according to the sum of indoor unit capacity which will be connected after the branch.
1) Y-joint
Classification
Model name
Specification
MBH
kW
Y-joint (E)
MXJ-YA1509M
51 and below
15.0 and below
MXJ-YA2512M
Over 51 ~ 136 and below
Over 15.0 ~ 40.0 and below
MXJ-YA2812M
Over 136 ~ 154 and below
Over 40.0 ~ 45.0 and below
MXJ-YA2815M
Over 154 ~ 240 and below
Over 45.0 ~ 70.3 and below
MXJ-YA3419M
Over 240 ~ 336 and below
Over 70.3 ~ 98.4 and below
MXJ-YA4119M
Over 336 ~ 461 and below
Over 98.4 ~ 135.2 and below
MXJ-YA4422M
Over 461
Over 135.2
2) Distribution
header
Classification
Model name
Specification
MBH
kW
Distribution header (E)
MXJ-HA2512M
154 and below (for 4 rooms)
45.0 and below (for 4 rooms)
MXJ-HA3115M
240 and below (for 8 rooms)
70.3 and below (for 8 rooms)
MXJ-HA3819M
Over 240 (for 8 rooms)
Over 70.3 (for 8 rooms)