Classification
Header joint connection
Y-joint / header joint connection
Maximum
allowable
length of
pipe
Outdoor
unit ~
Indoor units
Actual
Length
The distance between an outdoor unit and the farthest indoor unit ≤ 75 m (246’)
Ex) 8 indoor units
a+g≤ 75 m (246’)
Ex) 8 indoor units
a+b+c ≤ 75 m (246’)
Equivalent
length
The distance between an outdoor unit and the farthest indoor unit ≤ 90 m (295’)
Main pipe
length
The main pipe(a) from the outdoor unit to the first Y-joint should be less than
50 m (164’).
Total
length
The sum of total length of pipes should be less then 200 m (656’).
Maximum
allowable
height
Outdoor
unit ~
Indoor units
Height
H1: The difference in height between an outdoor unit and indoor unit < 30 m (98’)
Height
H2: The difference in height between indoor units ≤ 15 m (49’)
Maximum allowable
length after Y-joint
Actual
Length
The distance between the header joint
and the indoor unit ≤ 40 m (131’)
Ex) b, c ~ f, g ≤ 40 m (131’)
The distance between the first Y-joint and
the farthest indoor unit ≤ 40 m (131’)
Ex) 8 indoor units
b+c, d+g ≤ 40 m (131’)
H/P (AM072/096/120/144HXWA
✴
)
Classification
Single Installation
Module installation
Installing only with
Y-joint
Branch joint
Outdoor unit
Indoor unit
Branch joint
Outdoor unit
Indoor unit
Installing with Y-joint
and distribution
header
Branch joint
Distribution header
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Distribution header
Branch joint
Installing only with
distribution header
Outdoor unit
Indoor unit
Distribution header
Outdoor unit
Indoor unit
Distribution header