![Samsung KXWD Series Installation Manual Download Page 16](http://html1.mh-extra.com/html/samsung/kxwd-series/kxwd-series_installation-manual_4743204016.webp)
ENGLISH-16
Accessories
Accessories
f
You must keep following accessories until the installation is finished.
f
Hand over the installation manual to the customer after finishing the installation.
Installation manual
*Installation socket
❋
Models with packing socket: AM072/096/120HXWA
✴✴
.
❋
Socket can be different depending on the models.
Model number
Connection type
Heat recovery [mm (inch)]
Heat pump [mm (inch)]
Gas
Liquid
High-
pressure gas
Socket
needed
Gas
Liquid
Socket
needed
AM072HXWA
✴✴
(6 ton) (a)
Unit connection
22.22 (7/8)
9.52 (3/8)
19.05 (3/4)
Yes
19.05 (3/4)
9.52 (3/8)
No
Field connection
19.05 (3/4)
9.52 (3/8)
15.88 (5/8)
19.05 (3/4)
9.52 (3/8)
AM096HXWA
✴✴
(8 ton) (a)
Unit connection
22.22 (7/8)
9.52 (3/8)
19.05 (3/4)
No
19.05 (3/4)
9.52 (3/8)
Yes
Field connection
22.22 (7/8)
9.52 (3/8)
19.05 (3/4)
22.22 (7/8)
9.52 (3/8)
AM120HXWA
✴✴
(10 ton) (a)
Unit connection
28.58 (1-1/8) 9.52 (3/8)
22.22 (7/8)
No
22.22 (7/8)
9.52 (3/8)
Yes
Field connection
28.58 (1-1/8) 12.7 (1/2)
22.22 (7/8)
28.58 (1-1/8) 12.7 (1/2)
AM192HXWA
✴✴
(16 ton)
Unit connection
28.58 (1-1/8) 15.88 (5/8) 28.58 (1-1/8)
No
28.58 (1-1/8) 15.88 (5/8)
No
Field connection
28.58 (1-1/8) 15.88 (5/8) 28.58 (1-1/8)
28.58 (1-1/8) 15.88 (5/8)
(a) Cut socket as needed for 6, 8, and 10 ton units.
ID 19.05
(3/4)
ID 22.22
(7/8)
ID 25.4
(1)
ID 15.88
(5/8)
ID 19.05
(3/4)
ID 22.22
(7/8)
ID 28.58
(1 1/8)
Cutting line
Cutting line
unit: mm (inch)
k}tGzG~Tnlvptluki]_TW[^``hTWZUGGGX]