ENGLISH-93
0
2
INST
ALLING
THE
PRODUC
T
Optional item
Input unit
SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Setting long-
piping condition
(Setting is
unnecessary
if high-head
condition is set.)
Main
0
9
0
0
Disable (Factory default)
0
1
Long piping level 1
When equivalent length of
farthest indoor unit from
the outdoor unit is between
100~170 m (328’~558’)
0
2
Long piping level 2
When equivalent length of
farthest indoor unit from the
outdoor unit is over 170 m
(558’)
Energy saving
setting
Main
1
0
0
0
Disable (Factory default)
0
1
Enable
Energy saving mode starts
when the room temperature
reaches desired temperature
while operating in heating
mode.
Disable
Main
1
1
0
0
Disable
This function is not applicable
for this model
0
1
Disable
Expand
operational
temperature
range for cooling
operation
Main
1
2
0
0
Disable
0
1
Enable
Channel address
Main
1
3
A
U
Automatic setting (Factory
default)
Address for classifying the
product from upper level
controller (DMS, S-NET 3, etc)
0 ~ 15
Manual setting for channel
0~15
Disable
Main
1
4
0
0
Disable
This function is not applicable
for this model
0
1
Disable
Circulation water
flow control
Individual
1
5
0
0
Disable (Factory default)
0
1
7-10 V
When variable flow control
valve is applied
0
2
5-10 V
0
3
3-10 V