ENGLISH-57
0
2
INST
ALLING
THE
PRODUC
T
Electrical wiring work
Specification of the circuit breaker and power cable
Electric Characteristics
1. Heat Pump (1 phase 208 ~ 230V)
Nominal
Capacity (Ton)
Model name
Module 1
RLA
Power Supply
Comp 1
MCA
MOP
3 Ton
AM038KXWD
✴
16
20
35
4 Ton
AM048KXWD
✴
19.2
24
40
5 Ton
AM055KXWD
✴
20.8
26
45
2. Heat Pump (3 phase 208~230 V)
Nominal
Capacity
(Ton)
Model name
Module 1
Module 2
Module 3
RLA
Power Supply
RLA
Power Supply
RLA
Power Supply
Comp
1
Comp
2
MCA
MOP
Comp
1
Comp
2
MCA
MOP
Comp
1
Comp
2
MCA
MOP
6 Ton
AM072HXWAF
✴
12.8
16
25
8 Ton
AM096HXWAF
✴
18.4
23
40
10 Ton
AM120HXWAF
✴
24
30
50
12 Ton
AM144HXWAF
✴
12.8
16
25
12.8
16
25
14 Ton
AM168HXWAF
✴
12.8
16
25
18.4
23
40
16 Ton
AM192HXWAF
✴
17.6
17.6
39.6
50
18 Ton
AM216HXWAF
✴
18.4
23
40
24
30
50
20 Ton
AM240HXWAF
✴
24
30
50
24
30
50
22 Ton
AM264HXWAF
✴
12.8
16
25
17.6
17.6
39.6
50
24 Ton
AM288HXWAF
✴
18.4
23
40
17.6
17.6
39.6
50
26 Ton
AM312HXWAF
✴
24
30
50
17.6
17.6
39.6
50
28 Ton
AM336HXWAF
✴
12.8
16
25
12.8
16
25
17.6
17.6
39.6
50
30 Ton
AM360HXWAF
✴
12.8
16
25
18.4
23
40
17.6
17.6
39.6
50
32 Ton
AM384HXWAF
✴
17.6
17.6
39.6
50
17.6
17.6
39.6
50
34 Ton
AM408HXWAF
✴
18.4
23
40
24
30
50
17.6
17.6
39.6
50
36 Ton
AM432HXWAF
✴
24
30
50
24
30
50
17.6
17.6
39.6
50
38 Ton
AM456HXWAF
✴
12.8
16
25
17.6
17.6
39.6
50
17.6
17.6
39.6
50
40 Ton
AM480HXWAF
✴
18.4
23
40
17.6
17.6
39.6
50
17.6
17.6
39.6
50
42 Ton
AM504HXWAF
✴
24
30
50
17.6
17.6
39.6
50
17.6
17.6
39.6
50
48 Ton
AM576HXWAF
✴
17.6
17.6
39.6
50
17.6
17.6
39.6
50
17.6
17.6
39.6
50
(1) RLA is based on AHRI 1230 Cooling Standard Condition [Indoor Temp : 26.7 °C/80 °F(DB) / 19.46 °C/67 °F(WB),
Inlet Water Temp : 30 °C (86 °F)]
(2) Voltage Tolerance is ± 10 %
(3) Maxium allowable voltage between phases is 2 %
(4) Refer to module combination table for independent units information
Symbols
(1) RLA : Rated Load Ampere
(2) MCA : Minimum Circuit Ampere (A)
(3) MOP : Maxium Overcurrent Protective Device (A)
NOTE