Installing ducts going to / from outside
Installing the ducting to the weatherhoods
Outside weatherhoods
The weatherhoods must have built-in "bird" screens with 1/4 inch (6.35 mm) minimum mesh to prevent birds and rodents from
entering into the ductwork. Do not use smaller mesh as it will be very susceptible to plugging up. The preferred location of the
weatherhoods is:
• No less than 10 ft. (3 m) apart from each other.
• At least 18 inches (457.2 mm) above snow line or ground level.
• Supply hood must be kept away from sources of contaminants, such as automobile exhaust fumes, gas meters, garbage
cans, containers, cooling towers, tar roofs, etc.
• Avoid prevailing winds, whenever reasonably possible.
The outside perimeter of the weatherhood must be sealed to prevent leakage into the building.
Careful consideration should be given to selecting an outside hood with a face velocity low enough so as not to encourage the
migration of rain or snow into the ductwork.
Ducting from the weatherhoods –To and From the ERV
Galvanized sheet metal ducting with sufficient cross section with an integral single piece of insulated wrap with vapor barrier should be
used to connect the ERV to the weatherhoods. Insulated flex duct may be used in moderation, if sized and installed properly. (Consult
local codes)
A minimum R value of insulation should be equal to 4 (RSI 0.75) ,consult local codes.
All ducts should be sealed using a good bead of high quality caulking (preferably acoustical sealant) and a high quality aluminum
foil tape, or other approved duct sealant.
Installing Drain Line
Through normal operation and including defrost mode, the ERV may produce some condensation. This water should flow into a nearby
drain, or be taken away by a condensate pump. The ERV and all condensate lines must be installed in a space where the temperature is
maintained above the freezing point. A “P” trap should be made in the drain line. This will prevent odors from being drawn back up into the
unit.
Remove the drain spout, invert it so it protrudes from the botton of the unit and re-install in order to connect a condensate drain
Install the drain hose, making a “P” trap
If outdoor air temperature is above 32°F (0°C) at the extract air (30% RH/72°F, 30% RH /22°C), no drain line
installation is required. If this is the case keep the drain spout as shipped from factory with the cap.
6
Summary of Contents for Fresh Access AN035NSEDAV/AA
Page 16: ...Wiring Diagram AN035NSEDAV AA 14 AN035NSEDAV AA 24VAC field provided ...
Page 17: ...Wiring Diagram AN075NSEDAV AA 15 AN075NSEDAV AA 24VAC field provided ...
Page 18: ...Wiring Diagram AN120NSEDAV AA 16 AN120NSEDAV AA 24VAC field provided ...
Page 23: ...21 ...
Page 37: ...Connexions électriques AN035NSEDAV AA 35 AN035NSEDAV AA 24VAC field provided ...
Page 38: ...Connexions électriques AN075NSEDAV AA 36 AN075NSEDAV AA 24VAC field provided ...
Page 39: ...Connexions électriques AN120NSEDAV AA 37 AN120NSEDAV AA 24VAC field provided ...
Page 44: ......