Installation Verification Test
Without external control
1. Fan speed selector switch
• Set fan Speed selector switch to Standby.
2. Start-up
• Apply power to unit
• Unit should enter
Exhaust only defrost
mode for a 10 second duration and the following should occur:
Exhaust fan runs in HIGH (Normal) speed
Supply fan remains off
3. Standby
• Following the start-up unit should enter
Standby
mode. The following should occur:
Exhaust fan shuts off
Supply fan remains off
4. LOW (Reduced) speed
• Set fans speed selector switch LOW (Reduced) speed. The following should occur.
Exhaust fan runs in LOW (Reduced) speed
Supply fan runs in LOW (Reduced) speed
5. HIGH (Normal) speed
• Set fans speed selector switch HIGH (Normal) speed. The following should occur.
Exhaust fan ramps up to HIGH (Normal) speed
Supply fan ramps up to HIGH (Normal) speed
6. Test completion
•
Set fan speed selector switch to desired setting
•
Installation Verification test is complete
With external control
1. Start-up
• Apply power to unit
• Unit should enter
Exhaust only defrost
mode for a 10 second duration and the following should occur:
Exhaust fan runs in HIGH (Normal) speed
Supply fan remains off
2.
• Following start-up unit will respond to external control
• Consult user manual/instruction provided with external controller and ensure unit responds appropriately.
3. Test completion
• Installation Verification test is complete
18
Summary of Contents for Fresh Access AN035NSEDAV/AA
Page 16: ...Wiring Diagram AN035NSEDAV AA 14 AN035NSEDAV AA 24VAC field provided ...
Page 17: ...Wiring Diagram AN075NSEDAV AA 15 AN075NSEDAV AA 24VAC field provided ...
Page 18: ...Wiring Diagram AN120NSEDAV AA 16 AN120NSEDAV AA 24VAC field provided ...
Page 23: ...21 ...
Page 37: ...Connexions électriques AN035NSEDAV AA 35 AN035NSEDAV AA 24VAC field provided ...
Page 38: ...Connexions électriques AN075NSEDAV AA 36 AN075NSEDAV AA 24VAC field provided ...
Page 39: ...Connexions électriques AN120NSEDAV AA 37 AN120NSEDAV AA 24VAC field provided ...
Page 44: ......