Installation examples
(Cont'd)
* Drawings are illustrations only and actual port locations and airflow directions may vary, consult unit spec sheets.
It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended.
The amount of air (CFM) that an ERV will deliver is directly related to the total external static pressure (E.S.P.) of the system. Static pressure is
a measure of resistance imposed on the blower by length of duct work/number of fittings used in duct work, duct heater etc.
SUPPLY IN
EXHAUST OUT
ERV UNIT
RETURN AIR DUCT
AIR HANDLER UNIT
SUPPLY IN
BALANCING DAMPERS
SUPPLY IN
EXHAUST OUT
HRV UNIT
SUPPLY DUCT
EXHAUST AIR TO HRV UNIT
12" BREATHER SPACE
CEILING RETURN AIR PLENUM
AIR HANDLER UNIT
SUPPLY IN
BALANCING DAMPERS
Simplified Installation
• Stale air drawn from return of air handler
• Fresh air supplied to return of air handler, further down
stream of ERV exhaust
• Air Handler blower must operate when ERV is providing
ventilation
• ERV airflow should be balanced
Partially Dedicated System (Indirect Connections)
• Stale air drawn from areas of contamination
• Fresh air supplied into ceiling return air plenum or grille
• ERV airflow should be balanced
ERV UNIT
EXHAUST AIR TO ERV UNIT
9
Summary of Contents for Fresh Access AN035NSEDAV/AA
Page 16: ...Wiring Diagram AN035NSEDAV AA 14 AN035NSEDAV AA 24VAC field provided ...
Page 17: ...Wiring Diagram AN075NSEDAV AA 15 AN075NSEDAV AA 24VAC field provided ...
Page 18: ...Wiring Diagram AN120NSEDAV AA 16 AN120NSEDAV AA 24VAC field provided ...
Page 23: ...21 ...
Page 37: ...Connexions électriques AN035NSEDAV AA 35 AN035NSEDAV AA 24VAC field provided ...
Page 38: ...Connexions électriques AN075NSEDAV AA 36 AN075NSEDAV AA 24VAC field provided ...
Page 39: ...Connexions électriques AN120NSEDAV AA 37 AN120NSEDAV AA 24VAC field provided ...
Page 44: ......