39
SET
TING
(*4)
• [Cool mode]
– Err= Indoor temperature – Set temperature
– If Err > C+2, the modulating valve operates at the maximum voltage defined with SEG16,
the 02 series installation option. In other cases, the valve step is adjusted in accordance with
the formula given above.
• [Heat mode]
– Err= Set temperature – Indoor tempe f
❋
f = Heating compensation (correction) temperature (default : 2)
– If Err > C+2, the modulating valve operates at the maximum voltage defined with SEG16,
the 02 series installation option. In other cases, the valve step is adjusted in accordance with
the formula given above.
(*5)
– Cycle: 1 minute
– ΔErr = Err
n
– Err
n-1
– ΔV = D * ΔErr + E * Err
n
– New DCV output = Current DCV ΔV
05 series installation option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
5
Use Auto Change
Over for 4-pipe only
(When setting SEG3)
Standard heating
temp. offset
(When setting SEG3)
Standard cooling
temp. offset
(When setting SEG3)
Standard for mode
change Heating
→
Cooling
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
(When setting SEG3)
Standard for mode
change Cooling
→
Heating
(When setting SEG3)
Required time for
mode change
-
-
-
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
FCU KIT pipe
installation structure
-
Valve open control
when Thermo Off
-
FCU cool air
prevention
compensation
temperature
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
-
-
-
Setting cool/heat air
prevention skip
FCU KIT external
room sensor