44
O
THERS
Error code
Operation and error status can be checked by LED of FCU KIT.
Error code
R-LED
Y/G-LED
Error
Solutions
162
ON
OFF
EEPROM error
Change EEPROM
163
OFF
ON
Option input error
Reset option
Communication error
ON
ON
Communication error
(between interface modules
or wired remote controller)
Check communication
status between FCU KIT and
interface module or wired
remote controller
-
OFF
OFF
Power not supplied
Check power supply
-
Blinking Blinking
Normal
Error code
Error description
E121
Indoor temperature sensor error (Open/Short)
E990
Water-IN 1 sensor error (Open/Short)
E991
Water-IN 2 sensor error (Open/Short)
E101
Communication error between indoor and outdoor unit when there is no
communication for 2 minutes
E201
Communication error on interface module detection
-
Incomplete interface module tracking in 10 minutes
-
Mixed installation of FCU KIT and indoor unit
-
Exceeding maximum installation number of FCU KIT (16)
E108
Error on repeated communication address
E109
Uncomplete setting communication address
E992
Sensor detached or water blocked in Cool mode
E993
Sensor detached or water blocked in Heat mode
E198
Thermal fuse open error
E162
EEPROM error
E163
EEPROM option error
LED
Troubleshooting
Summary of Contents for DVM