18
INS
T
ALLA
TION
FCU KIT power cable specification
This specification is when installing a FCU KIT.
Europe
Power supply
Power cable
Ground wire
Communication cable
ELCB
AC 220 - 240 V~ 50 Hz, 1 Ph
Min. 2.5 mm
2
(0.0039 inch
2
)
Min. 2.5 mm
2
(0.0039 inch
2
)
Min. 0.75 mm
2
(0.0012 inch
2
)
15 A
Part
Rated Capacity
Fan (High, Mid, Low)
AC 220 - 240 V~ 50 Hz, 1 Ph, 1 A
Water Valve
AC 220 - 240 V~ 50 Hz, 1 Ph, 0.5 A
USA
Power supply
MCA
MOP
AC 208 - 230 V~ 60 Hz, 1 Ph
2.75
15 A
Part
Rated Capacity
Fan (High, Mid, Low)
AC 208 - 230 V~ 60 Hz, 1 Ph, 1 A
Water Valve
AC 208 - 230 V~ 60 Hz, 1 Ph, 0.5 A
DC Wire
Part
Rated Capacity
Remote controller
DC 12 V
External contact
Zero voltage contact input
Sensor cable
NTC ./10 kΩ 25 °C
y
Purpose of control: Operating control
y
Construction of control: Independently mounted control
y
Rated impulse voltage: 2500 V