38
SET
TING
Option
SEG13
SEG14
SEG15
SEG16 (*3)
SEG17 (*4)
SEG18 (*5)
Description
Page
Use of external control
Setting the output of external
control
Operation voltage of Modulating Valve
Temperature difference of
the Modulating Valve Step
Control Output
Modulating Valve Control
Coefficient
Display/detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Min. (V)
Max. (V)
C(°C)
D
E
0
Disuse
0
Thermo ON
0
5
10
0
2
0
2
1
1
ON/OFF control
1
4
10
1
2.5
1
2.5
1
2
OFF control
2
3
10
2
3
2
3
1
2
3
Window ON/OFF
control
1
Operation ON
3
2
10
3
3.5
3
1
1
4
5
9
4
4
4
2
1.5
5
4
9
5
4.5
5
2.5
1.5
6
3
9
6
5
6
3
1.5
7
2
9
7
1.5
7
1
1.5
8
5
8
8
1
8
2
0.5
9
4
8
9
0.5
9
2.5
0.5
A
3
8
A
0
A
3
0.5
B
2
8
B
1
0.5
C
5
7
C
2
2
D
4
7
D
2.5
2
E
3
7
E
3
2
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Description
Page
-
Heating setting compensation
offset
-
-
-
Display/detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
3
-
0
0 °C (0 °F)
-
-
-
1
2 °C (3.6 °F)
2
5 °C (9 °F)
(*1) Minimal fan operation when Thermo Off
• Fan operates for 20 seconds every 5 minutes in Heat mode.
• Fan stops in Cool mode.
(*2)
• If the voltage of the low fan speed is set higher than that of the high fan speed, the
voltage of the low fan speed is restricted by the voltage of the high fan speed.
e.g. If the setting is High 5 V and Mid 6 V,
→
the actual voltage becomes High 5 V and Mid 5 V.
(*3)
• Recommended: If it is the maximum voltage, the valve must be wide open.
• Required: If it is the minimum voltage, the valve must be open.
Setting address of FCU KIT and installation option