40
SET
TING
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Description
Page
Mode
Use Auto Change Over for
4-pipe only
(When setting SEG3) Standard
heating temp. offset
(When setting SEG3) Standard
cooling temp. offset
(When setting SEG3) Standard
for mode change Heating
→
Cooling
Display/
detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
0
5
0
Follow product
option
0
0 °C (0 °F)
0
0 °C (0 °F)
0
1 °C (1.8 °F)
1
Use Auto
Change Over
for 4-pipe only
1
0.5 °C (0.9 °F)
1
0.5 °C (0.9 °F)
1
1.5 °C (2.7 °F)
2
1 °C (1.8 °F)
2
1 °C (1.8 °F)
2
2 °C (3.6 °F)
3
1.5 °C (2.7 °F)
3
1.5 °C (2.7 °F)
3
2.5 °C (4.5 °F)
4
2 °C (3.6 °F)
4
2 °C (3.6 °F)
4
3 °C (5.4 °F)
5
2.5 °C (4.5 °F)
5
2.5 °C (4.5 °F)
5
3.5 °C (6.3 °F)
6
3 °C (5.4 °F)
6
3 °C (5.4 °F)
6
4 °C (7.2 °F)
7
3.5 °C (6.3 °F)
7
3.5 °C (6.3 °F)
7
4.5 °C (8.1 °F)
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Description
Page
(When setting SEG3) Standard
for mode change Cooling
→
Heating
(When setting SEG3) Required
time for mode change
-
-
-
Display/
detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
Display
Detail
1
0
1 °C (1.8 °F)
0
5 min.
-
-
-
1
1.5 °C (2.7 °F)
1
7 min.
2
2 °C (3.6 °F)
2
9 min.
3
2.5 °C (4.5 °F)
3
11 min.
4
3 °C (5.4 °F)
4
13 min.
5
3.5 °C (6.3 °F)
5
15 min.
6
4 °C (7.2 °F)
6
20 min.
7
4.5 °C (8.1 °F)
7
30 min.
Setting address of FCU KIT and installation option
Summary of Contents for DVM