42
2
Space requirements
2-3. Installing duct for horizontal exhaust discharge
It is necessary to install an air-discharge duct (field supply) to direct exhaust from the fan horizontally if it is difficult to provide a
minimum space of 2m(6.6 ft) between the air-discharge duct outlet and a nearby obstacle.
2-4. Installing the outdoor unit in harsh environments
In abnormally harsh environments such as cold and/or windy areas, sufficient countermeasures to guard against excessive wind
and snow should be taken to ensure the unit's correct operation. Snow-proof duct (field supply) should be fitted to the unit and
direct exposure to the wind should be avoided as much as possible. When the unit is expected to operate in cooling mode in
condition under 10°C(50°F), in snowy areas, in environments subject to strong winds or rain, install air inlet and outlet ducting as
shown in the below example
Discharged air
Louver
Suction air
Upper floor
Discharged air
Ex) Balcony
Ex) Mechanical room
The frame/foundation should be higher than expected snowfall.
The foundation must be solid and the unit must be secured with anchor bolts.
Be sure to install unit in a place strong enough to withstand its weight.
When installing on a roof subject to strong wind, countermeasures must be taken to prevent the unit form being
overturned.
Any lack of strength may cause unit to fall down, resulting in a personal injury.
For more detailed information about installation, refer to installation manual.
CAUTION
Summary of Contents for DVM PLUS III
Page 1: ...Outdoor Units SAMSUNG DVM Air Conditioner DVM PLUS III 2010 North America for 60Hz...
Page 2: ......
Page 3: ...Outdoor Units...
Page 6: ...4 DVM PLUS III...
Page 7: ...5 Products I Products 1 Outdoor units 6 2 Indoor units 9 3 Accessories 11...
Page 62: ...DVM DVM Technical Data Book...
Page 63: ......