6
Refrigerant piping works
Pipe size between branch joints : (B)
Tempers of pipe
Select the pipe size according to the capacity sum of indoor units
which are connected below this pipe.
Pipe size between branch joints and indoor unit (C)
Select the pipe size according to the indoor unit’s capacity.
Branch joiat : (D), (E), (F)
Branch joint of outdoor unit’s multi connection (D)
First branch joint (E)
Select branch joint according to the outdoor unit’s capacity.
Branch joint (F)
Select the pipe size according to the capacity sum of
indoor units which are connected below this pipe.
1) Y-joint
2) Header joint
Total Indoor unit’s
capacity
Pipe size (O.D)
Liquid
Gas
mm
inches
mm
inches
51MBH
Ø9.52
Ø3/8
Ø15.88
Ø5/4
51~79MBH
Ø19.05
Ø3/4
79~96MBH
Ø22.23
Ø7/8
96~138MBH
Ø12.70
Ø1/2
Ø28.58 Ø1-1/8
138~160MBH
160~240MBH
Ø15.88
Ø5/8
240~336MBH
Ø19.05
Ø3/4
Ø34.93 Ø1-3/8
336~468MBH
Indoor unit’s
capacity
Pipe size (O.D)
Liquid
Gas
mm
inches
mm
inches
6~20MBH
Ø6.35
Ø1/4
Ø12.70
Ø1/2
24~48MBH
Ø9.52
Ø3/8
Ø15.88
Ø5/8
Outdoor multi
connection
Model
Capacity of outdoor
unit
branch joint (D)
MXJ-T3819K
12 ~ 30 Ton
Y-joint
(E)
Model
Capacity of outdoor unit
MXJ-YA2512K
6, 8,10 Ton
MXJ-YA2812K
12 Ton
MXJ-YA2815K
14,16,18,20 Ton
MXJ-YA3119K
22, 24, 26, 28 Ton
MXJ-YA3819K
30 Ton
Header
joint
(F)
Model
Total Indoor unit’s
capacity
The connect-
able quantity of
indoor units
MXJ-HA2512K 160 MBH and below
4
MXJ-HA3115K Over 160 MBH~ 240 MBH
8
MXJ-HA3819K Over 240 MBH
8
Pipe size
Thickness
Material
mm
inches
mm
inches
Ø6.35
Ø1/4
0.7
0.027
C1220T-O
(Annealed)
Ø9.52
Ø3/8
Ø12.70
Ø1/2
0.8
0.031
Ø15.88
Ø5/8
1.0
0.039
Ø19.05
Ø3/4
0.9
0.035
C1220T-1/2H
(Drawn temper)
Ø22.23
Ø7/8
Ø25.40
Ø1
1.0
0.039
Ø28.58 Ø1-1/8
1.1
0.043
Ø31.75 Ø1-1/4
Ø34.93 Ø1-3/8
1.2
0.047
Ø38.10 Ø1-1/2
1.35
0.053
Ø44.45 Ø1-3/4
1.6
0.062
Ø50.80
Ø2
2.0
0.079
Y-joint
(F)
Model
Capacity of outdoor unit
MXJ-YA1509K 51 MBH and below
MXJ-YA2512K Over 51 MBH ~ 138 MBH and below
MXJ-YA2812K Over 138 MBH ~ 160 MBH and below
MXJ-YA2815K Over 160 MBH ~ 240 MBH and below
MXJ-YA3119K Over 240 MBH ~ 336 MBH and below
MXJ-YA3819K Over 336 MBH ~ 468 MBH and below
Make sure to use C1220T-1/2H pipe for more than
Ø19.05mm(3/4
in
). In case of using C1220T-O pipe
for Ø19.05mm(3/4
in
) pipe may be broken, which
can result in an injury.
CAUTION
Summary of Contents for DVM PLUS III
Page 1: ...Outdoor Units SAMSUNG DVM Air Conditioner DVM PLUS III 2010 North America for 60Hz...
Page 2: ......
Page 3: ...Outdoor Units...
Page 6: ...4 DVM PLUS III...
Page 7: ...5 Products I Products 1 Outdoor units 6 2 Indoor units 9 3 Accessories 11...
Page 62: ...DVM DVM Technical Data Book...
Page 63: ......