6-3. Piping examples
Classification
Branch with Y-joint
Branch with Y and Header joint
Branch with Header joint
One outdoor unit
installed
Multiple outdoor
units installed
Items
Examples
Remarks
Max.
piping
length
Outdoor
~
Indoor unit
Piping
(Equivalent
piping)
200m(656ft)
220m(722ft)
Branch with Y joint
a+b+c+d+e+f+g+p
≤
200(220)m / 656(722)ft
Equivalent pipe length
Y-joint:0.5m(1.6ft),
Header:1m(3.2ft)
Branch with Y joint
and Header joint
a+i+k
≤
200(220)m / 656(722)ft
a+b+h
≤
200(220)m / 656(722)ft
Branch with
header joint
a+i
≤
200(220)m / 656(722)ft
Total piping
1000m
(3281ft)
Branch with Y joint a+b+c+d+e+f+g+p+h+i+j+k+l+m+n
≤
1000m / 3281ft
Branch with Y joint
and Header joint
a+b+c+d+e+f+g+p+h+i+j+k
≤
1000m / 3281ft
Branch with
Header joint
a+b+c+d+e+f+g+p+h+i
≤
1000m / 3281ft
Outdoor
~
Outdoor unit
Piping
10m(33ft)
r
≤
10 (33ft), s
≤
10 (33ft), t
≤
10m (33ft)
Equivalent
piping
13m(43ft)
r
≤
13 (43ft), s
≤
13 (43ft), t
≤
13m (43ft)
Level
difference
Outdoor ~
Indoor unit
Piping
50m(164ft)
40m(131ft)
H1
≤
50m (164ft) / 40m (131ft)
Indoor ~
Indoor unit
Piping
15m(49ft)
H2
≤
15m (49ft)
Outdoor ~
Outdoor unit
Piping
5m(16ft)
H3
≤
5m (16ft)
Allowable
length
after
branch
The first
branch
~
the farthest
indoor unit
Piping
45m(148ft)
b+c+d+e+f+g+p
≤
45 m(148ft), i
≤
45m(148ft)
Piping
90m(295ft)
It needs to satisfy required conditions
Only apply
DVM PLUS
III
(DVM PLUS
III
HR
exclusion)
Distribution kit
Model
Remarks
Allowable
From distribution kit to
indoor unit
3m
(10ft)
MEV-A13SA / MEV-A16SA (For 1 indoor unit)
For wall-mounted &
ceiling indoor unit
From distribution kit to
indoor unit
20m
(66ft)
MXD-A13K116A / MXD-A13K200A / MXD-A16K200A /
MXD-A22K200A (For 2 indoor units)
MXD-A13K216A / MXD-A13K300A / MXD-A16K213A /
MXD-A16K300A (For 3 indoor units)
Required condition
Example
The first branch
joint ~
the farthest
indoor unit
If the sum of pipe length (b+c+d+e+f+g+p) is over 45m (148ft), (but
not exceed : 90m/295ft) increase pipe size of b,c,d,e,f,g (b,c,d,e,f,g :
pipe 1 size up)
Total pipe length
If main pipe size is not increased,a+bx2+cx2+dx2+ex2+fx2+gx2+h+i
+j+k+l+m+n+p
≤
1000m (3281ft)
If main pipe size is not increased, ax2+bx2+cx2+dx2+ex2+fx2+gx2+h
+i+j+k+l+m+n+p
≤
1000m (3281ft)
Each Y-joint ~
each indoor
h,I,j,..p
≤
45m (148ft)
Between
indoor units
The difference between the distance of the outdoor unit to the farthest
indoor unit and the distance of the outdoor unit to the farthest indoor
unit
≤
45m (148ft) (a+b+c+d+e+f+g+p)-(a+h)
≤
45m (148ft)
G
F
h
i
j
k
l
m
n
b
a
c
d
e
f
g
p
b
a
c
d
e
f
g
h
i
k
j
b
a
c
d
e
f
g
h
i
G
F
h
i
j
k
l
m
n
b
a
c
d
e
f
g
p
b
a
c
d
e
f
g
h
i
k
j
b
a
c
d
e
f
g
h
i
G
F
h
i
j
k
l
m
n
b
a
c
d
e
f
g
p
6
Refrigerant piping works
Summary of Contents for DVM PLUS III
Page 1: ...Outdoor Units SAMSUNG DVM Air Conditioner DVM PLUS III 2010 North America for 60Hz...
Page 2: ......
Page 3: ...Outdoor Units...
Page 6: ...4 DVM PLUS III...
Page 7: ...5 Products I Products 1 Outdoor units 6 2 Indoor units 9 3 Accessories 11...
Page 62: ...DVM DVM Technical Data Book...
Page 63: ......