Wiring works

5-1. External connection diagram of DVM PLUS 

III

1)  3 phase 3 wires

R

S

T

N

R

S

T

N

OF1 OF2

OF1 OF2

3 phase 3 wires  

(208~230V)

3 phase 3 wires 

(208~230V)

Communication 

cable among 

outdoor units

208~230V

208~230V

Indoor Outdoor

Outdoor

Communication 

cable between 

indoor and  

outdoor units

Earth

Earth

Earth

Earth

Main unit

Sub unit

Indoor

MCCB

+ELB

or 

ELCB

MCCB

+ELB

or 

ELCB

 

•   Connect the power cable of the outdoor unit after checking that R-S-T(3 phase 3 wires) is properly connected. 

 

•  The communication cable between indoor and outdoor units has no polarity.

 

•  Arrange the cables using cable ties.

Summary of Contents for DVM PLUS III

Page 1: ...Outdoor Units SAMSUNG DVM Air Conditioner DVM PLUS III 2010 North America for 60Hz...

Page 2: ......

Page 3: ...Outdoor Units...

Page 4: ...ories I Products 6 9 11 1 2 3 4 5 6 7 8 Specifications Dimensional drawing PCB connector layout Electrical wiring diagram Sound pressure level Operation limit Cycle operation mode Cycle function parts...

Page 5: ...on 1 2 3 4 5 6 7 8 Outdoor unit combinations Space requirements Placing the outdoor units Electric specifications Wiring works Refrigerant piping works Option switches function keys Error codes III In...

Page 6: ...4 DVM PLUS III...

Page 7: ...5 Products I Products 1 Outdoor units 6 2 Indoor units 9 3 Accessories 11...

Page 8: ...PLUS III HR Airflow direction Upward airflow T Frontward airflow F Mode Heat Pump H Heat Recovery R Rating voltage 1 220 240V 50Hz E 3 208 230V 60Hz F 3 380 415V 50Hz G 3 380V 60Hz H 3 460V 60Hz J Ver...

Page 9: ...16 HP 15 0 17 5 20 0 Model Name RVXVHT150 175 200FE TON 18 HP 22 5 Model Name RVXVHT225FE TON 20 HP 25 0 Model Name RVXVHT250FE TON 22 24 HP 27 5 30 0 Model Name RVXVHT275 300FE TON 26 HP 32 5 Model...

Page 10: ...Ton Capacity HP Model Single unit 6 7 5 RVXVHT075FE 8 10 0 RVXVHT100FE 10 12 5 RVXVHT125FE Classification Capacity Ton Capacity HP Basic model RVXVHT075FE RVXVHT100FE RVXVHT125FE Module unit 12 15 0...

Page 11: ...lim S Middle Static Pressure U Wall mounted type Neo Forte N Vivace V Capacity 1 10 kW 3 digits Rating voltage 1 220V 60Hz B 1 208V 230V 60Hz C 1 220V 240V 50Hz E Version Export A Z Domestic KOREA 0 9...

Page 12: ...2 2 Line up Model name Notation 020 023 032 040 052 060 072 100 110 145 MBH 6 0 7 5 9 5 12 0 18 0 20 0 24 0 30 0 36 0 48 0 Slim 1 way cassette Mini 4 way cassette 4 way cassette Slim duct MSP duct Viv...

Page 13: ...10A DVM PLUS II DVM PLUS III FJM ERV Individual control system Controller Wireless remote controller MR BH01U Cassette Duct Receiver needed Wired remote controller Multi function MWR WE00 Cassette Wal...

Page 14: ...for 9 rooms EEV kits MXD A13K116 Below 12MBH 1 unit 18MBH 24MBH 1 unit Wall mounted Ceiling For 2 indoor units Option MXD A13K200 Below 12MBH 2 units MXD A16K200 18MBH 24MBH 2 units MXD A22K200 Over...

Page 15: ...II Outdoor units 1 Specifications 14 2 Dimensional drawing 20 3 PCB connector layout 22 4 Electrical wiring diagram 24 5 Sound pressure level 25 6 Operation limit 28 7 Cycle operation mode 29 8 Cycle...

Page 16: ...rmer Current Transformer Current Transformer Fan motor Voltage Protection Fan motor Voltage Protection Fan motor Voltage Protection Piping Connections Liquid mm 9 52 9 52 12 70 inch 3 8 3 8 1 2 Gas mm...

Page 17: ...545 4 095 3 545 Output kW 6 94 5 83 6 94 5 83 Lubricant Type 3MAF POE 3MAF POE Charging cc 1 685 1 685 1 685 1 685 fl oz 57 57 57 57 Fan Type Control Propeller BLDC Propeller BLDC Motor Output W 630 x...

Page 18: ...F POE 3MAF POE Charging cc 1 685 1 685 1 685 1 685 1 685 1 685 fl oz 57 57 57 57 57 57 Fan Type Control Propeller BLDC Propeller BLDC Motor Output W 630 x 2 630 x 2 Airflow Rate m3 min 170 x 2 170 x 1...

Page 19: ...711 4 095 3 545 Output kW 7 91 7 91 6 94 5 83 Lubricant Type 3MAF POE 3MAF POE Charging cc 1 685 1 685 1 685 1 685 fl oz 57 57 57 57 Fan Type Control Propeller BLDC Propeller BLDC Motor Output W 630...

Page 20: ...3MAF POE 3MAF POE Charging cc 1 685 1 685 1 685 1 685 1 685 1 685 fl oz 57 57 57 57 57 57 Fan Type Control Propeller BLDC Propeller BLDC Motor Output W 630 x 3 630 x 3 Airflow Rate m3 min 170 x 3 170...

Page 21: ...MAF POE 3MAF POE Charging cc 1 685 1 685 1 685 1 685 1 685 1 685 fl oz 57 57 57 57 57 57 Fan Type Control Propeller BLDC Propeller BLDC Motor Output W 630 x 3 630 x 3 Airflow Rate m3 min 170 x 1 180 x...

Page 22: ...communication wiring conduit 34 50 knock out hole hole side 5 Power communication wiring conduit 34 50 knock out hole hole front 14 Power communication wiring conduit 27 80 knock out hole hole side 6...

Page 23: ...ication wiring conduit 34 50 knock out hole hole side 5 Power communication wiring conduit 34 50 knock out hole hole front 14 Power communication wiring conduit 27 80 knock out hole hole side 6 Power...

Page 24: ...r 13 CN70 Black AC 208 230V Input 14 CN76 Yellow Comp 1 CCH 15 CN15 White Comp 2 CCH 16 CN81 Black Oil Valve 1 17 CN82 Yellow Oil Valve 2 18 CN80 Red Liquid Bypass valve for FVI compressor No CN COLOR...

Page 25: ...Input 35 GT2 White Power Trans In AC 208 230V 36 CN703 Black AC 208 230V Output 37 CN501 White Main BLDC Driver PCB Connector 38 CN101 White Motor Signal 39 CN301 White Motor Power No CN COLOR FUNCTIO...

Page 26: ...ical wiring diagram 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 38 39 40 41 42 43 36 37 K13 K14 Unit option On On MAIN unit On Off SUB 1 unit Off On...

Page 27: ...60 55 50 45 40 35 30 25 63 125 250 500 1000 2000 4000 8000 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 Sound pressure level dB Octave band center frequency Hz 70 NC 65 65 60 55 50 45 40 35 30 25 63 125...

Page 28: ...evel dB Octave band center frequency Hz 70 NC 65 65 60 55 50 45 40 35 30 25 63 125 250 500 1000 2000 4000 8000 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 Sound pressure level dB Octave band center freq...

Page 29: ...000 2000 4000 8000 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 Sound pressure level dB Octave band center frequency Hz 70 NC 65 65 60 55 50 45 40 35 30 25 63 125 250 500 1000 2000 4000 8000 NC 60 NC 55...

Page 30: ...86 Outdoor temperature C F DB Range for operation Range for pull down operation Indoor temperature C F DB 6 Operation limit 25 77 20 68 15 59 10 50 5 41 0 32 5 23 10 14 15 5 20 4 10 50 15 59 20 68 25...

Page 31: ...pressor 22 V EVI EEV Electronic Expansion Valve 23 W Turbo Intercooler 24 X EVI_in temperature sensor 25 Y EVI_out temperature sensor 26 Z Liquid tube temperature sensor 27 a EVI bypass pilot solenoid...

Page 32: ...ersing valve Check Check valve Service Service valve Angle ball type 3 Switch Heater Pressure Switch High pressure switch Mechanical type Heater H Electric heater 4 Others Compressor DVI Digital Vapor...

Page 33: ...31 Outdoor units 7 2 Cycle diagrams 1 RVXVHT075 100FE DVM PLUS III 6 8 TON s s H H E s E s A B D E F H I J L M N O P Q R S T V W X Y Z a b c e f h i j m n o s u d s s s k p K C G U g r q t v...

Page 34: ...32 Cycle operation mode 7 2 RVXVHT125FE DVM PLUS III 10 TON s s H H E s E s A B D E F H I J p L M N O P R S V W X Y Z a b c e f i j m n o K s d s s s k Q g h C r q T U G t v u...

Page 35: ...3 EEV kits Indoor units 1 MXD series 3 Indoor units 2 MEV series s u b a E E w u s x y z E x y z b a s a E s u b a E E E 2 rooms Indoor units with built in EEV Indoor units without EEV Wall mounted 3...

Page 36: ...ndoor unit Outdoor unit Cooling operation Heating operation Low temperature pressure liquid High temperature pressure gas High temperature pressure liquid Low temperature pressure gas s H H E s E s s...

Page 37: ...unit Outdoor unit Cooling operation Heating operation Low temperature pressure liquid High temperature pressure gas High temperature pressure liquid Low temperature pressure gas E E E E E E Heating H...

Page 38: ...lve bracket Liquid service valve Cond_out temp sensor Hot gas bypass valve High pressure sensor DVI Digital Vapor Injection compressor 1 Low pressure sensor Oil separator High pressure switch Liquid b...

Page 39: ...ssor Discharge temperature sensor Oil balancing valve bracket Sump Base temp sensor FVI Fixed Vapor Injection compressor 1 Liquid bypass valve for FVI compressor Liquid bypass valve for DVI compressor...

Page 40: ...nd_out temp sensor It has application to know subcooling and the complete point of defrost 12 Main EEV 1 2 It controls the amount of refrigerant entering outdoor s heat exchanger in heating operation...

Page 41: ...allation 1 Outdoor unit combinations 40 2 Space requirements 41 3 Placing the outdoor units 44 4 Electric specifications 45 5 Wiring works 46 6 Refrigerant piping works 48 7 Option switches function k...

Page 42: ...4 8 10 10 12 5 RVXVHT125FE 60 156 0 14 Classification Capacity Ton Capacity HP Basic model Total capacifities of the connectable indoor units MBH Maximum number of connectable indoor units RVXVHT075FE...

Page 43: ...ricted 20 3 4 or more 300 12 or more 10 3 8 or more Front 600 24 or more Front 20 3 4 or more 10 3 8 or more 500 20 or more 20 3 4 or more 300 12 or more 10 3 8 or more 300 12 or more 20 3 4 or more 1...

Page 44: ...ould be avoided as much as possible When the unit is expected to operate in cooling mode in condition under 10 C 50 F in snowy areas in environments subject to strong winds or rain install air inlet a...

Page 45: ...22 880 34 5 8 1050 41 3 8 1588 62 1 2 2256 88 7 8 668 26 1 4 532 21 871 34 1 4 765 30 1 8 550 21 5 8 220 8 5 8 105 4 1 8 880 34 5 8 1049 41 1 2 2227 87 11 16 252 9 7 8 417 16 3 8 252 9 7 8 1100 43 1...

Page 46: ...r washer and stopper nut from compressors with a tool 3 Refasten the nut washer only Nut washer Washer Stopper nut Remove Model RVXVHT075 100 RVXVHT125 A 880 34 5 8 1200 47 1 4 B 738 29 1058 41 5 8 A...

Page 47: ...87 253 122 2 60 60 23 4 24 6 2 0 63 0 63 7 7 RVXVHT275FE 60 208 230 187 253 155 7 50 50 50 13 8 21 8 19 6 21 8 2 0 63 0 63 0 63 7 7 7 RVXVHT300FE 60 208 230 187 253 161 4 50 50 50 19 6 21 8 3 0 63 0 6...

Page 48: ...units 208 230V 208 230V Indoor Outdoor Outdoor Communication cable between indoor and outdoor units Earth Earth Earth Earth Main unit Sub unit Indoor MCCB ELB or ELCB MCCB ELB or ELCB Connect the powe...

Page 49: ...iddle frame Connecting the ring terminal of 3 phase cable CV Connecting the ring terminal of 3 phase cable FCV A B C A B C A B 250mm C A B C Make sure that all wiring should not contact with piping li...

Page 50: ...rant and oil like next diagram Outdoor joint kits should be installed in a horizontal direction even it is a low pressure pipe When the piping length between outdoor and branch joints is 2m 6 6 ft or...

Page 51: ...49 Installation 6 2 Example of piping layouts Example of piping layouts for DVM PLUS III Using Y joint Using Header joint...

Page 52: ...g p 45 m 148ft i 45m 148ft Piping 90m 295ft It needs to satisfy required conditions Only apply DVM PLUS III DVM PLUS III HR exclusion Distribution kit Model Remarks Allowable From distribution kit to...

Page 53: ...10 12 5 A1 12 70 1 2 28 58 1 1 8 18 22 5 A2 15 88 5 8 28 58 1 1 8 26 32 5 A3 19 05 3 4 34 93 1 3 8 A1 Pipes to the outdoor unit Liquid Gas A2 Pipes between outdoor joint kits Liquid Gas A3 Main pipes...

Page 54: ...l Capacity of outdoor unit branch joint D MXJ T3819K 12 30 Ton Y joint E Model Capacity of outdoor unit MXJ YA2512K 6 8 10 Ton MXJ YA2812K 12 Ton MXJ YA2815K 14 16 18 20 Ton MXJ YA3119K 22 24 26 28 To...

Page 55: ...HT075FE 6 5 14 330 RVXVHT100FE 7 5 16 535 RVXVHT125FE 9 0 19 824 Additional refrigerant charging of distribution kit kg m kg m lbs ft Remarks Regardless of the liquid pipe size additional refrigerant...

Page 56: ...0 1 64 31 75 1 1 4 0 55 1 80 34 93 1 3 8 0 58 1 90 38 10 1 1 2 0 60 1 97 41 30 1 5 8 0 70 2 30 44 45 1 3 4 0 75 2 46 50 80 2 0 80 2 62 6 6 Equivalent length calculations Equivalent length calculation...

Page 57: ...Off On 33 0 469 3236 Off Off 27 0 384 2647 SW05 K13 K14 Outdoor unit s address On On Outdoor unit s address No 1 Main unit On Off Outdoor unit s address No 2 Sub I unit Off On Outdoor unit s address N...

Page 58: ...ther the pipe connection of MCU correspond with indoor unit s address in HR system K 8 BLANK BLANK Push 5th time Judgment system of refrigerant amount K 9 BLANK BLANK Push 6th time Return to normal vi...

Page 59: ...2nd detection 16 E 153 Floating switch error of indoor unit 2nd detection 17 E 154 RPM feed back error of indoor unit 18 E 155 RPM feed back error of indoor unit The second motor of indoor unit 19 E...

Page 60: ...2 is detached from the sensor hold of the pipe 54 E 264 Discharge temperature sensor of compressor 3 compressor is detached from the sensor hold of the pipe 55 E 265 Sump Base temperature sensor of ma...

Page 61: ...scheduler Centralized controller 101 E 606 COM1 COM2 communication setting error Wired remote controller 102 E 607 Two masters of wired remote controllers were installed in one COM2 communication line...

Page 62: ...DVM DVM Technical Data Book...

Page 63: ......

Page 64: ...r notice for the continuous product improvement Samsung Electronics Co LTD Digital Air Solution Business Team SE Dept Head Office Suwon Korea 416 Maetan 3Dong Yeongtong Gu Suwon City Gyeonggi Do Korea...

Reviews: