Setting an indoor unit address (MAIN/RMC)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display) should be connected to an indoor unit to receive option.
3. Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
4. Assign an indoor unit address by wireless remote controller.
- The initial setting status of indoor unit ADDRESS(MAIN/RMC) is “0A0000-100000-200000-300000”.
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Setting Main
address
100-digit of indoor
unit address
10-digit of indoor
unit
The unit digit of an
indoor unit
Remote
Controller
Display
Indication
and
Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0
A
0
No Main
address
0~9
100-digit
0~9
10-digit
0~9
A unit
digit
1
Main
address
setting
mode
Option SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
Setting RMC
address
Group
channel(*16)
Group address
Remote
Controller
Display
Indication
and
Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
1
0
No RMC
address
RMC1
0~2
RMC2
0~F
1
RMC
address
setting
mode
t
When “A”~”F” is entered to SEG5~6, the indoor unit MAIN ADDRESS is not changed.
t
If you set the SEG 3 as 0, the indoor unit will maintain the previous MAIN ADDRESS even if you input the option
value of SEG5~6.
t
If you set the SEG 9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the option value
of SEG11~12.