Installation options for the 05 series (detailed)
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Function
Page
Mode
Use of Auto
Change Over for HR
only in Auto mode
(When setting SEG3)
Offset for the
heating reference
temperature
(When setting
SEG3)
Offset for
the cooling
reference
temperature
(When setting
SEG3)
Reference for
change from
Heat mode to
Cool mode
Indication
and
details
Indication Details Indication
Details
Indication
Details
Indication
Details
Indication Details Indication Details
0
5
0
Follow
product
option
0
0
0
0
0
1
1
0.5
1
0.5
1
1.5
2
1
2
1
2
2
1
Use 'Auto
Change
Over' for HR
only
3
1.5
3
1.5
3
2.5
4
2
4
2
4
3
5
2.5
5
2.5
5
3.5
2
Setting
the
indoor
unit for
cooling
only
6
3
6
3
6
4
7
3.5
7
3.5
7
4.5
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Function
Page
(When setting SEG3)
Reference for change
from Cool mode to
Heat mode
(When setting
SEG3)
Time required for
mode change
Compensation
option for a long
pipe and the height
difference between
indoor units
MTFC (*3)
-
Indication
and
details
Indication Details Indication
Details
Indication
Details
Indication
Details
Indication Details
-
1
0
1
0
5 min.
0
The default
value is
used.
0
Disuse
1
1.5
1
7 min.
1
1) The height
difference (*1)
is more than
30 m.
- or -
2) The
distance (*2)
is longer than
110 m.
2
Use
2
2
2
9 min.
3
2.5
3
11 min.
4
3
4
13 min.
2
1) The height
difference (*1)
is 15 to 30 m.
- or -
2) The
distance(*2) is
50 to 110 m.
5
3.5
5
15 min.
6
4
6
20 min.
7
4.5
7
30 min.
Summary of Contents for AM071NN1DEH/TL