Installation Procedure
English
Installation Pr
oc
edur
e
Example of Installation
Ɵͱϩɇ̷Χͱиʪθʀɇɵ̷ʪ̷ʪ͝˝ϩ˵ø॔ߣߢߢ࣑͔࣒ࡥÃ̈͝ϩ̈ɇ̷ΧЇ̷̷ࣛ̈͝ʀЇθθʪ͝ϩ॔ߣߢࣈࣉࡥŵЇ̈͝͝͝˝ʀЇθθʪ͝ϩͱ˙ʪɇʀ˵Ї̈͝ϩϑ॔ߣࣈࣉࡥƟͱϩɇ̷ߣߢ̈͝ʒͱͱθ
units were installed
or
10 [A]
ELCB
MCCB+ELB
9 [A]
1 [A]
0[m]
10[m]
20[m]
100[m]
Indoor unit 1
Indoor unit 2
Indoor unit
࡛
Apply following equation.
n
Coef×35.6×L
k
×i
k
ॣ࣑
) <
10% of input voltage[V]
k=1
1000×A
k
࡛
Calculation
ࣞ
Installing with 1 sort wire.
2.5 [mm
2
]
2.5 [mm
2
]
-2.2 [V]
-2.0 [V]
220 [V]
-(2.2+2.0+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-11.2 [V]
208.8 [V] :
Applicable
Within 198V
to 242V
······· 2.5 [mm
2
] ·······
ࣞ
Installing with 2 different sort wire.
4.0 [mm
2
]
4.0 [mm
2
]
-1.4 [V]
-1.2 [V]
220 [V]
-(1.4+1.2+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-10.5 [V]
209.5 [V] :
Applicable
Within 198V
to 242V
······· 2.5 [mm
2
] ·······
CAUTION
࡛
Select the power cable in accordance with relevant
local and national.
࡛
Wire size must comply with local and national code.
࡛
You should connect the power cable into the power
cable terminal and fasten it with a clamp.
࡛
The unbalanced power must be maintained within 10%
of supply rating among whole indoor units.
࡛
If the power is unbalanced greatly, it may shorten
the life of the condenser. If the unbalanced power is
exceeded over 10% of supply rating, the indoor unit is
protected, stopped and the error mode indicates
࡛
Connect the power cable to the auxiliary circuit breaker.
An all pole disconnection from the power supply must be
̈͝ʀͱθΧͱθɇϩʪʒ̈͝ϩ˵ʪ˙̈уʪʒӥθ̈͝˝࣑क़ߥ͔͔࣒
࡛
You must keep the cable in a protection tube.
࡛
Maximum length of power cables are decided within
10% of power drop. If it exceeds, you must consider
another power supplying method.
࡛
The circuit breaker(MCCB, ELB) should be considered
more capacity if many indoor units are connected from
one breaker.
࡛
Use round pressure terminal for connections to the
power terminal block.
࡛
For wiring, use the designated power cable and
connect it firmly, then secure to prevent outside
pressure being exerted on the terminal board.
࡛
Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
strip the head and make proper tightening impossible.
࡛
Over-tightening the terminal screws may break them.
࡛
See the table below for tightening torque for the
terminal screws.
Step 13 Optional: Extending the power
cable
1
Prepare the following tools.
Tools
Spec
Shape
Crimping pliers
MH-14
Connection sleeve
(mm)
20xØ6.5
(HxOD)
Insulation tape
Width 19
mm
Contraction tube
(mm)
70xØ8.0
(LxOD)