![Samsung AM071NN1DEH/TL Instruction Manual Download Page 19](http://html1.mh-extra.com/html/samsung/am071nn1deh-tl/am071nn1deh-tl_instruction-manual_4745204019.webp)
19
English
Installation Pr
oc
edur
e
Norminal
dimensions
for cable
(mm²)
Norminal
dimensions
for screw
(mm)
B
D
d1
E
F
L
d2
t
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min.
Min. Max.
Standard
dimension
(mm)
Allowance
(mm)
Min.
1.5
4
6.6
± 0.2
3.4
+0.3
-0.2
1.7
± 0.2
4.1
6
16
4.3
+0.2
0
0.7
4
8
2.5
4
6.6
± 0.2
4.2
+0.3
-0.2
2.3
± 0.2
6
6
17.5
4.3
+0.2
0
0.8
4
8.5
4
4
9.5
± 0.2
5.6
+0.3
-0.2
3.4
± 0.2
6
5
20
4.3
+0.2
0
0.9
Specifications of the terminal blocks
(Unit: mm)
AC power: M4 screw
Communication: M3.5 screw
11
13
7.5
9.0
18
13
.8
Power supply
(single phase)
MCCB
ELB
Min : 198V
Max : 242V
XA
XA, 30 mA
0.1 s
Power cable
Earth cable
Communication
cable
2.5 mm or more
2.5 mm²
0.75 to 1.5 mm²
Decide the power cable specification and maximum
length by formula
2
.
1
Decide the capacity of ELB and MCCB by below
formula.
Ɵ˵ʪʀɇΧɇʀ̈ϩцͱ˙kø9ࡥđAA9ǹࣈࣉ॔ߣߤߧǹߣߣǹנ̈
NOTE
࡛
X : The capacity of ELB, MCCB
࡛ נ̈ࡤƊЇ͔ͱ˙θɇϩ̈͝˝ʀЇθθʪ͝ϩϑͱ˙ʪɇʀ˵̈͝ʒͱͱθЇ̈͝ϩ
Rated currents
Model
Rating current(A)
đߢߣߩĘĘߣťk²७
0.14
đߢߤߤĘĘߣťk²७
0.15
đߢߤߤĘĘߣUk²७
0.20
đߢߤߪĘĘߣUk²७
0.23
đߢߥߨĘĘߣUk²७
0.25
đߢߧߨĘĘߣUk²७
0.28
đߢߩߣĘĘߣUk²७
0.40
2
Decide the power cable specification and maximum
length within 10% voltage drop among indoor units.
n
Coef×35.6×Lk
× ik)
< 10% of input voltage[V]
ॣ࣑
1000×Ak
k=1
NOTE
࡛
Coef: 1.55
࡛
Lk: Distance among each indoor unit[m], Ak: Power
cable specification[mm
2
]
࡛
ik: Running current of each unit[A]
Summary of Contents for AM071NN1DEH/TL