40
3) If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and change
the function for the selected option.
▶
4) After selecting the function for options, press and hold the K2 switch for 2 seconds. Edited value of the option will be
saved when entire segments blinks and tracking mode begins.
• Edited option will not be saved if you do not end the option setting as explained in above instruction.
CAUTION
❋
While you are setting the option, you may press and hold the K1 button to reset the value to previous setting.
❋
If you want to restore the setting to factory default, press and hold the K4 button while you are in the option setting mode.
- If you press and hold the K4 button, setting will be restored to factory default but it doesn’t mean that restored setting is
saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress, setting will be saved.
Optional item
Input unit
SEG1
SEG2
SEG3
SEG4
Function of the option
Remarks
Unused
option
Main
0
0
0
0
Unused option
Unused option by this model
Cooling
capacity
correction
Main
0
1
0
0
7-9
Targeted evaporation
temperature [°C].
(When low temperature
value is set, discharged air
temperature of the indoor
unit will decrease)
0
1
5-7 (Factory default)
0
2
9-11
0
3
10-12
0
4
11-13
0
5
12-14
0
6
13-15
Capacity
correction for
heating
Main
0
2
0
0
3.0 (Factory default)
Targeted high pressure [MPa].
(When low pressure
value is set, discharged air
temperature of the indoor
unit will decrease)
0
1
2.5
0
2
2.6
0
3
2.7
0
4
2.8
0
5
2.9
0
6
3.1
0
7
3.2
0
8
3.3
Current
restriction
rate
Main
0
3
0
0
100% (Factory default)
When restriction option is
set, cooling and heating
performance may decrease.
0
1
95 %
0
2
90 %
0
3
85 %
0
4
80 %
0
5
75 %
0
6
70 %
0
7
65 %
0
8
60 %
0
9
55 %
1
0
50 %
1
1
No restriction
Oil collection
interval
Main
0
4
0
0
Factory default
0
1
Shorten the interval by 1/2
Temperature
to trigger
defrost
operation
Main
0
5
0
0
Factory default
0
1
Apply setting when the
product is being installed
in humid area such as near
river or lake
The defrost option shortens
the starting time of the defrost
operation