36
Installing grounding wire
X
Grounding must be done by a qualified installer for your safety.
X
Use the grounding wire by referring to the specification of the electric cable of the outdoor unit.
Grounding the power cable
X
The standard of grounding may vary according to the rated voltage and installation place of the air conditioner.
X
Ground the power cable according to the following.
Installation place
Power condition
High humidity
Average humidity
Low humidity
Voltage of lower than 150V
Perform the grounding work
3.
Note 1)
Perform the grounding work 3 if
possible for your safety.
Note 2)
Voltage of higher than 150V
Must perform the grounding work 3.
Note 1)
(In case of installing circuit breaker as well)
1)
Grounding work 3
• Grounding must be done by your installation specialist.
• Check if the grounding resistance is lower than 100Ω. When installing a circuit breaker that can cut the electric
circuit within 0.5 second in case of a short circuit, the allowable grounding resistance should be 30~500Ω.
2)
Grounding at dry place
• The grounding resistance is should be lower than 100Ω. (It should not be higher than 250Ω)
- Use the rated grounding wire by referring to the specification of the electric cable of the outdoor unit.
NOTE
Performing the grounding work
X
Use the grounding wire by referring to the specification of the electric cable for the outdoor unit.
When using the terminal for grounding only
When using grounding of the switch board
Earth terminal
Switch Board