28
Refrigerant pipe installation
Insulating refrigerant pipe or Y-joint
X
You must check if there is a gas leak before completing all the installation process. After you check that the gas does not
leak, you must insulate the pipe and hose.
X
Use EPDM insulation which meets the following condition.
Item
Unit
Standard
Density
g/cm
3
0.048~0.096
Dimension change route by heat
%
-5 or less
Water absorption rate
g/cm
3
0.005 or less
Thermal conductivity
kcal/m·h·˚C
0.032 or less
Moisture transpiration factor
ng/(m²·s·Pa)
15 or less
Moisture transpiration grade
g/(m²·24h)
15 or less
Formaldehyde dispersion
mg/L
-
Oxygen rate
%
25 or more
Selecting the insulation of refrigerant pipe
X
Insulate the gas pipe and liquid pipe by referring to the thickness of insulator for each pipe size.
X
The standard condition is 30°C(86°F), with humidity less than 85%. In the conditions of high humidity, use one grade
thicker.
Pipe
Pipe size [mm (inch)]
Insulation(Cooling, Heating)
Remarks
Standard
[30°C (86°F),
Below 85%]
High humidity
[30 °C (86°F),
85% or more]
EPDM, NBR
Liquid pipe
Ø6.35 ~ Ø9.52 (1/4 ~ 3/8)
9t
I
Heat resisting
temperature is more
than 120°C (248°F)
Ø12.70 ~ Ø50.80 (1/2 ~ 2)
13t
I
Gas pipe
Ø6.35 (1/4)
13t
19t
Ø9.52 (3/8)
19t 25t
Ø12.70 (1/2)
Ø15.88 (5/8)
Ø19.05 (3/4)
Ø22.23 (7/8)
ki]_TW__]_hTWXptk}tGzGljvG䖐㨴㥐㛨ὤhhluUGGGY_
YWYWTWZTY^GGG㝘䟸GYaX[aZZ