85
ENGLISH
Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Function of the option
Remarks
Unused option
Main
1
5
0
0
Unused option
Unused option by this model
Unused option
Main
1
6
0
0
Unused option
Unused option by this model
Speed operation
Main
1
7
0
0
Disabled (Factory default)
Enabling this setting will
command the air conditioner to
cool faster at initial start-up .
However, this function will not
work when High-head condition
setting or Long-piping condition
setting is enabled .
0
1
Enabled
Max . capacity
restriction
(B type PBA)
Main
1
8
0
0
Enabled (Factory default)
Restrict excessive capacity
increase when operating indoor
units with small capacity
0
1
Disabled
Gasleak
Pumpdown
(B type PBA)
Main
1
9
0
0
Disabled (Factory default)
If the gas leak occurred it should
be entered in the pumpdown
operation .
0
1
Enabled
Unused option
Main
2
0
0
0
Unused option
Unused option by this model
LA KIT option
(B type PBA)
Main
2
1
0
0
Disabled (Factory default)
Set when LA KIT is installed .
0
1
Enabled
Emergency
operation for
indoor unit
communication
error (B type PBA)
Main
2
2
0
0
Disabled (Factory default)
When set, emergency operation
is possible even if an indoor
communication error occurs .
0
1
Indoor high humidity
condition (operating for up
to 12hours)
0
2
Indoor low humidity
condition (operating for up
to 24hours)
❋
❋
There is a risk of water leakage during emergency operation for indoor unit communication error . Please be careful when
using it .