46
Refrigerant pipe installation
Classification
Model name of
indoor unit
Number of units
Unit amount of
refrigerant [kg/EA
(lb/EA)]
Amount of
additional
refrigerant [kg (lb)]
Total amount
of additional
refrigerant [kg (lb)]
①
②
①
×
②
∑(
①
×
②
)
Indoor unit (
ⓑ
)
4way cassette
(AM018FN4DCH)
4
0 .45 (0 .99)
1 .8 (3 .96)
ⓑ
3 .30 (7 .26)
Slim duct
(AM024FNLDCH)
2
0 .45 (0 .99)
0 .90 (1 .98)
Slim duct
(AM012FNLDCH)
1
0 .35 (0 .77)
0 .35 (0 .77)
1way cassette
(AM012FN1DCH)
1
0 .25 (0 .55)
0 .25 (0 .55)
- Total amount of refrigerant (
ⓐ
+
ⓑ
) = 5 .575 + 3 .30 = 8 .875 (kg)
= 12 .19 + 7 .26 = 19 .45 (lb)
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter
Minimum thickness
Temper grade
mm
inch
mm
inch
6 .35
1/4
0 .70
0 .028
Annealed
9 .52
3/8
0 .70
0 .028
12 .70
1/2
0 .80
0 .031
15 .88
5/8
1 .00
0 .039
19 .05
3/4
0 .90
0 .035
Drawn
22 .22
7/8
0 .90
0 .035
25 .40
1
1 .00
0 .039
28 .58
1 1/8
1 .10
0 .043
31 .75
1 1/4
1 .10
0 .043
34 .92
1 3/8
1 .21
0 .048
38 .10
1 1/2
1 .35
0 .053
41 .28
1 5/8
1 .43
0 .056
44 .45
1 3/4
1 .60
0 .063
50 .80
2
2 .00
0 .079
53 .98
2 1/8
2 .10
0 .083
• For pipes larger than Ø 3/4" (Ø 19 .05mm), drawn type (C1220T-1/2H or C1220T-H) type copper pipe must be
used . If a annealed type (C1220T-O) copper pipe is used, pipe may break due to its low pressure resistance and
cause personal injury .
CAUTION