23
ENGLISH
Model name for combination
AM740MXVAJC2AZ
AM760MXVAJC2AZ
AM780MXVAJC2AZ
AM800MXVAJC2AZ
Number of individual outdoor units
3
3
3
3
Combined outdoor unit
AM080MXVAJC
AM100MXVAJC
AM120MXVAJC
AM140MXVAJC
AM160MXVAJC
AM180MXVAJC
1
1
AM200MXVAJC
AM220MXVAJC
2
1
AM240MXVAJC
AM260MXVAJC
AM280MXVAJC
1
1
AM300MXVAJC
1
1
2
1
Nominal capacity
Cooling (kW)
207 .2
213 .0
218 .4
224 .2
Cooling (Btu/h)
707 000
726 800
745 200
765 000
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
103 .6
106 .5
109 .2
112 .1
Minimum (Btu/h)
353 500
363 400
372 600
382 500
Maximum (kW)
269 .4
276 .9
283 .9
291 .5
Maximum (Btu/h)
919 100
944 800
968 800
994 500
Maximum number of connectable indoor
units
64
64
64
64
❋
❋
You can connect maximum 64 indoor units to the outdoor unit . Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address . Indoor unit address can be assigned from 0~63 . If the
indoor unit address was assigned from 64~79 E201 error will occur .
• Installation combination must be complied when composing outdoor unit combination .
CAUTION