20
Preparing for installation
Model name for combination
AM180MXVAJC/AZ AM200MXVAJC/AZ AM220MXVAJC/AZ AM240MXVAJC/AZ AM260MXVAJC/AZ
Number of individual outdoor units
1
1
1
1
1
Combined outdoor unit
AM080MXVAJC
AM100MXVAJC
AM120MXVAJC
AM140MXVAJC
AM160MXVAJC
AM180MXVAJC
1
AM200MXVAJC
1
AM220MXVAJC
1
AM240MXVAJC
1
AM260MXVAJC
1
AM280MXVAJC
AM300MXVAJC
Nominal capacity
Cooling (kW)
50 .4
56 .0
61 .6
67 .2
72 .8
Cooling (Btu/h)
172 000
191 100
210 200
229 300
248 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
25 .2
28 .0
30 .8
33 .6
36 .4
Minimum (Btu/h)
86 000
95 500
105 100
114 600
124 200
Maximum (kW)
65 .5
72 .8
80 .1
87 .4
94 .6
Maximum (Btu/h)
223 600
248 400
273 200
298 100
322 900
Maximum number of connectable indoor
units
32
36
40
43
47
Model name for combination
AM280MXVAJC/AZ AM300MXVAJC/AZ AM320MXVAJC2AZ AM340MXVAJC2AZ AM360MXVAJC2AZ
Number of individual outdoor units
1
1
2
2
2
Combined outdoor unit
AM080MXVAJC
AM100MXVAJC
1
AM120MXVAJC
1
AM140MXVAJC
1
AM160MXVAJC
AM180MXVAJC
AM200MXVAJC
AM220MXVAJC
1
1
1
AM240MXVAJC
AM260MXVAJC
AM280MXVAJC
1
AM300MXVAJC
1
Nominal capacity
Cooling (kW)
78 .6
84 .0
89 .6
95 .2
101 .6
Cooling (Btu/h)
268 200
286 600
305 700
324 800
346 700
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
39 .3
42 .0
44 .8
47 .6
50 .8
Minimum (Btu/h)
134 100
143 300
152 900
162 400
173 400
Maximum (kW)
102 .2
109 .2
116 .5
123 .8
132 .1
Maximum (Btu/h)
348 700
372 600
397 400
422 200
450 700
Maximum number of connectable indoor
units
51
54
58
61
64
Summary of Contents for AM MXVAFC Series