Selecting installation location
Decide the installation location, with the consideration of the following conditions, under user’s approval .
f
f
Place where hot discharge air or noise from the outdoor unit may not disturb the neighbor (Especially in residential areas,
keep the operation hours in mind .)
f
f
Place where structure can bear the weight and vibration of the outdoor unit .
f
f
Place with flat surface where rainwater does not settle or leak .
f
f
Place where it is not exposed to strong wind .
f
f
Well ventilated place with sufficient service place for repairs and maintenance . (Discharge duct can be purchased separately)
f
f
Place where you can connect the refrigerant pipes between indoor and outdoor units within allowable distance .
f
f
Place where there is no risk of inflammable gas leakage .
f
f
Place where there is no direct influence of snow or rain .
f
f
Place where a large amount of water generated by external environment does not directly affect the top of the outdoor
unit .
Installation Guide at the seashore
Make sure to follow below guides when installing at the seashore .
1 . Do not install the product in a place where it is directly exposed to sea water and sea breeze .
- Make sure to install the product behind a structure (such as building) that can block see breeze .
- Even when it is inevitable to install the product in seashore, make sure that product is not directly exposed to sea
breeze by installing a protection wall .
※
As we cannot guarantee that the corrosion resistance model(AM***MXVAFCAAZ) can prevent corrosion completely, we
recommend that you install a protection wall or install the outdoor unit behind a structure(such as building) that can
block sea breeze .
2 . Consider that the salinity particles clinging to the external panels should be sufficiently washed out .
3 . Because the residual water at the bottom of the outdoor unit significantly promotes corrosion, make sure that the slope
does not disturb drainage .
- Keep the floor level so that rain does not accumulate .
- Be careful not to block the drain hole due to foreign substance
4 . When product is installed in seashore, periodically clean it with water to remove attached salinity .
5 . Make sure to install the product in a place that provides smooth water drainage .
Especially, ensure that the base part has good drainage .
6 . If the product is damaged during the installation or maintenance, make sure to repair it .
7 . Check the condition of the product periodically .
- Check the installation site every 3 months and perform anti-corrosion treatment such as R-Pro supplied by SAMSUNG
(Code : MOK-220SA) or commercial water repellent grease and wax, etc ., based on the product condition .
- When the product is to be shut down for a long period of time, such as off-peak hours, take appropriate measures like
covering the product .
8 . If the product installed within 500m of seashore,
- Standard model (AM
✴✴✴
MXVAFC/AZ) : Special anti-corrosion treatment is required .
- Corrosion resistance model (AM
✴✴✴
MXVAFCAAZ) : Special anti-corrosion treatment is recommended .
※