74
Pipe insulation
Insulate the refrigerant pipe
f
f
Make sure to insulate the refrigerant pipe, branch joint, distribution header, and the connection part of the pipes .
f
f
If you insulate the pipes, condensed water will not fall from the pipes .
f
f
Check if there are any cracks on the insulation at the bent part of the pipe .
Fix securely without any gap .
Install the insulation to be
overlapped
Indoor unit
Insulator
Insulator
Clamp
Liquid side pipe
Gas side pipe
Insulator
Insulating pipes
Insulating pipes connected behind the EEV kit
• The insulation of the gas and liquid pipes can be in contact
with each other but they should not press excessively against
each other .
• When the gas side and liquid side pipes are contacting each
other, increase the thickness of the insulation by one grade .
• When installing the gas side and liquid side pipes, leave at
least 10mm (3/8") of space .
• When the gas side and liquid side pipes are contacting each
other, increase the thickness of the insulation by one grade .
Gas pipe
Liquid pipe
Insulator
Insulator
Gas pipe
10mm (3/8")
10mm (3/8")
10mm (3/8")
Liquid pipe
• Install the insulation without any gaps or cracks and
use adhesive on the connection part of it to prevent
moisture from entering .
• Bind the refrigerant pipe with insulation tape if it
is exposed to outside sunlight . (When binding the
pipe with finishing tape, be careful not to reduce the
thickness of the insulation .)
• Install the refrigerant pipe respecting that the
insulation does not get thinner on the bent part or
hanger of pipe .
• When the thickness of insulation is reduced, reinforce
the reduced thickness with additional insulation .
Insulator for refrigerant
pipe
a x 3
Hanger
Additional Insulator
a
CAUTION