. Installation
Selecting installation location
f
Choose a location with ventilation ducts or openings to remove the heat generated from the product and maintain the
surrounding temperature within: Hydro unit: 5 ~ 40 °C (41 ~ 104 °F), humidity 80 % Hydro unit HT: 5 ~ 35 °C (41 ~ 95 °F),
humidity 80 % .
f
Choose a place where the structure can bear the weight and vibration of the DVM Hydro unit / Hydro unit HT .
f
Choose a flat place that rainwater does not settle or leak .
f
Choose a well ventilated place with sufficient space for repair and other services .
f
Choose a place where you can easily connect the refrigerant pipes between the DVM Hydro unit / Hydro unit HT and outdoor
unit within allowable distance .
f
Do not install this product in a place where it may corrode .
f
Install the DVM Hydro unit / Hydro unit HT power and communication cables to the outdoor unit at least 1 m (3 .28 feet) away
from electric appliances such as TVs . In some cases interference may occur even if there's more than 1 m (3 .28 feet) gap from
the electric appliances .
Space requirement
f
When installing the product, make sure to secure minimum clearance with obstacles as shown below .
f
When you install one product on top of the other one, secure at least 600 mm (23 .6 inch) of space on the water pipe side .
Service space (Front)
10
0 (
3 .
9)
330 (13 .0)
600 (23 .6)
400 (15 .7)
518 (20 .4)
300 (11 .8)
Service space
(Side)
Installation
space for pipe
Product
Unit: mm (inch)