Hydro Unit HE
2.. Specification
Model CODE
AM096CNBDCH/AA
AM144CNBDCH/AA
Power Supply
Φ, #, V, Hz
1,2,208-230,60
1,2,208-230,60
Mode
-
HEAT PUMP
HEAT PUMP
Performance
Capacity
(Nominal)
Heating
108,000
172,000
Power
Power Input
(Nominal)
W
Heating
10
10
Current Input
(Nominal)
A
Heating
0.05
0.05
Heat Exchanger
Type
-
PHE
PHE
Quantity
-
1
1
Pipe Size
Φ, inch
NPT 1
NPT 1-1/4
Water Flow Rate
LPM
92
150
GPM
24.3
39.6
Flow Switch
LPM
30
50
GPM
7.9
13.2
Option Code
-
01004C-105000
231C1C-332200
01004C-105000
232D2D-332200
Piping
Connections
Liquid Pipe
Φ, inch
3/8
1/2
Gas Pipe
Φ, inch
7/8
1 1/8
Drain Pipe
Field
Wiring
Power Source Wire
Transmission Cable
Refrigerant
Type
-
R410A
R410A
Control Method
-
EEV INCLUDED
EEV INCLUDED
Sound
Sound Pressure
dB(A)
28
31
Dimensions
Net Weight
lbs
75.4
95.2
Shipping Weight
lbs
80.0
99.9
Net Dimensions (W×H×D)
inch
20.4x24.7x13.0
20.4x24.7x13.0
Shipping Dimensions (W×H×D)
inch
25.7x27.6x16.8
25.7x27.6x16.8
Temp
Max. Outdoor Ambient
Operating Temp.
Heating
95
95
Operating Water Temp. Range
68~122
68~122
℉
℉
Heating
Btu/h
3/4
3/4
AWG
10
10
AWG
18
18
Φ, inch
Min.
NOTE
*
Specifications may be subject to change without prior notice for product improvement.
*
1) Nominal heating capacities are based on;
Water temperature : 86°F(30°C) inlet, 95°F(35°C) outlet
Indoor temperature : 68°F(20°C) DB
Outdoor temperature :44.6°F(7°C) DB, 42.8°F(6°C) WB
*
2) Sound pressure was acquired in an anechoic room. Thus actual noise level may be different depending on the installation conditions.
*
3) The VRF system contains R410A (GWP=2,088) which is fluorinated greenhouse gas.
*
Heat Exchanger type : Plate Heat Exchanger (STS)