Hydro Unit HT
4. Capacity Table
8TON DVM S TDB Heat Capacity Table
C
ombination,%
(Capacity index)
Outdoor Temperature(℉)
Indoor Temperature(℉,DB)
68℉
TC
PI
DB
WB
Btu/h
kW
100%
-4
-6
90,422
10.24
1
0
95,881
10.45
5
3
99,293
10.67
10
9
101,341
10.62
14
12
104,753
10.4
19
18
106,459
9.57
23
21
107,482
8.99
27
25
107,482
8.15
32
30
107,482
7.68
37
36
107,482
7.25
41
39
107,482
6.88
45
43
107,482
6.7
48
46
107,482
6.38
52
50
107,482
6.08
55
54
107,482
5.81
59
57
107,482
5.61
Flowrate Information
Flowrate[gpm]
**048**
**072**
ΔT = 27℉
4.1
6.4
ΔT = 18℉
6.1
9.5
ΔT = 9℉
12.2
19.0
Combination 1 ( Outdoor Unit 8TON + Indoor Unit 4TON x 2ea)
PI Outdoor Unit(8TON)[kW]
6.70
PI System[kW]
11.54
= Total Indoor Unit PI + Outdoor Unit PI
Outdoor Unit Capacity Table
54,500
= HT Capacity Table (Ref. P.17)
= 2 x 5HP
109,000
2.419
= HT Capacity Table (Ref. P.17)
= 2 x 5HP
PI Total Indoor Unit[kW]
4.838
Indoor Heat Capa.[kW]
Indoor Heat Capa.[kW]
PI Indoor Unit(4TON)[kW]