MAINTENANCE
77
English
Error display
f
Segment will display error code (4 digit).
HYDRO-UNIT_MODULE_CHILLER
K1
K2
K3
K4
K5
K6
88-SEG DISPLAY
Display
Description
101
Communication error between hydro
controller and inverter controller
(If not received for 3 minutes from outdoor
unit)
108
Error due to repeated setting address
109
Communication error of hydro controller
address not complete
122
Error on hydro Evap in Sensor (Open/Short)
123
Error on hydro Evap out Sensor (Open/
Short)
128
Error on hydro Evap in Sensor (Detached)
129
Error on hydro Evap out sensor (Detached)
144
Error on hydro pipe temperature 2 sensor
145
Error on hydro EVA OUT 2 sensor
151
Hydro EEV open error (2nd detection)
152
Error due to closed EEV of hydro (2nd
detection)
153
Error on hydro floating switch (2nd
detection)
162
Inverter controller EEPROM error
163
Hydro controller EEPROM option setting
error
198
Error due to disconnected thermal fuse
(Temperature of terminal block increases.)
201
Communication error between hydro
controller and inverter controller
Display
Description
202
Communication error between hydro
controller and inverter controller (When
there is no response from indoor units after
tracking is completed)
203
Communication error of Main and sub
MICOM of inverter controller
205
Communication error of inverter
controller main PBA - sub PBA (Sub PBA
communication all not received)
206
Communication error of inverter
controller main PBA - sub PBA (Sub PBA
communication partially not received)
Specification of PBA display for actual
communication error
C001: Hub PCB communication error
C002: Fan PCB communication error
C003: INV1 communication error
C004: INV2 communication error
221
Error on outdoor temperature sensor (Short
or Open)
231
Error on COND outlet sensor (Short or Open)
241
COND outlet sensor is detached
251
Error on discharge temperature of COMP1
(Short or Open)
257
Error on discharge temperature of COMP2
(Short or Open)
262
Discharge temperature sensor of COMP1 is
detached
263
Discharge temperature sensor of COMP2 is
detached
266
Top1 temperature sensor is detached
267
Top2 temperature sensor is detached
269
Suction temperature sensor is detached
270
Suction 2 temperature sensor is detached
276
Error on Top 1 temperature sensor (Short or
Open)
Summary of Contents for AG042KSVANH
Page 113: ...MAINTENANCE 113 English Memo ...