INS
TALLA
TION
Water pipe installation
26
English
Securing water storage
Minimum water storage
Chilled/
heating
water pump
Buffer tank
Fan coil
f
If the length of water pipe is too short, water storage
within the system becomes lower and ON/OFF
operation of the compressor occurs more often. For
stable operation, maintain certain water storage by
applying header or Buffer tank.
CAUTION
ŷ
When installing tank, inlet pipe of the tank must be
installed under the water level.
f
If total water storage becomes under the minimum
storage, install another tank to retain more water
storage.
- In case of variable flow system, retain certain
amount of water by bypass pipe system.
Model name
Minimum water storage (L)
AG042KSV Series
294
AG056KSV Series
392
AG070KSV Series
490
NOTE
ŷ
Total water storage in the system = water storage
within the water pipe + water storage in DVM
C water storage in AHU (or fan coil)
ŷ
Minimum capacity of buffer tank = Minimum
water storage - Total water storage in the system
excluding buffer tank
ŷ
Select the capacity of buffer tank according to
system installation condition of the field.
Water amount within the DVM CHILLER: AG042
✴✴✴
,
AG056
✴✴✴
: 12liter / AG070
✴✴✴
: 15.3 liter
Water pipe installation
Connecting water pipe
Chilled/heating water inlet
Chilled/heating water outlet
Flange
f
Companion flange is not supplied. Use field supplied
one in DIN standardized product.
f
When connecting the water pipe, use companion
flange and bolt made of SUS304, DIN PN10
standardized product.
f
Maintain the tightening torque for flange as the table.
Water pipe
size
Allowable torque for
flange (N·m)
Material of
gasket
40 A
6.8
EPDM
50 A
12.7
EPDM
D
C
G
t
f
d
Size
D
t
W.N.
Slip-On
Blind
DIN PN10
40
150
16
16
16
50
165
18
18
18
G
f
d
Bolting
C
Diameter of
holes
Bolt size
DIN PN10
88
3
44.5
110
18
4-M16
102
3
57
125
18
4-M16