In
St
alla
tI
on
9
English
Specifications of the pump integrated models
Model
aG042KSVGnH
aG056KSVGnH
aG070KSVGnH
Power supply
3 Phase 4 Wires 380 ~ 415 V, 50/60 Hz
Capacity
Cooling (Rated)
kW
42
56
65
Heating (Rated)
kW
42
56
69.5
Power
consumption
Cooling (Rated)
kW
13.59
20.14
28.26
Heating (Rated)
kW
12.77
18.48
25.84
operating
current
Cooling (Rated)
a
24.2
34.2
45.8
Heating (Rated)
a
23.4
32.4
43.3
Refrigerant
type
R-410A
R-410A
R-410A
Charging amount
kg
18
18
18
Water
side heat
exchanger
type
Plate type heat exchanger
Flow rate
(Cooling/Heating)
lPM
120/120
160/160
186/200
Maximum operating
pressure
MPa
1.0
1.0
1.0
Head loss
kPa
60
100
120
Inlet·outlet connected
pipe size
a
40
40
50
Pump
type
End-Suction
Input x n
kW
1.68
1.68
1.68
output x n
W
1.45
1.45
1.45
normal Water Flow rate
(Cooling/Heating)
lPM
120/120
160/160
186/200
l/s
2.0/2.0
2.7/2.7
3.1/3.3
External Static Pressure
(Max.)
maq
22.4 / 22.4
15.3 / 15.3
10.2 / 10.2
kPa
220 / 220
150 / 150
131 / 100
Minimum water quantity
l
294
392
490
net weight
kg
472
472
493
net dimension
W X H X D
mm
1795 X 1695 X
765
1795 X 1695 X
765
1795 X 1695 X
765
Remote control
Module Control
Water outlet
temperature
range
Cooling (If using brine)
°C
5 ~ 25(-10 ~ 25)
5 ~ 25(-10 ~ 25)
5 ~ 25(-10 ~ 25)
Heating
°C
25 ~ 55
25 ~ 55
25 ~ 55
Surrounding
temperature
range
Cooling
°C
-15 ~ 48
-15 ~ 48
-15 ~ 48
Heating
°C
-25 ~ 43
-25 ~ 43
-25 ~ 43
MCa
a
39
53
65
MFa
a
50
60
75
1) Standard for rated cooling capacity: chilled water inlet/outlet temperature 12/7 °C, outdoor 35 °C DB, 24 °C WB
2) Standard for rated heating capacity: heating water inlet/outlet temperature 40/45 °C, outdoor 7 °C DB, 6 °C WB
3) When using brine, maintain the concentration according to temperature. (Refer to page 76.)
DB68-05916A-09_IM_DVM Chiller Outdoor_EU_EN_.indd 9
2022-05-02 오전 8:59:55