English
K2 (number of
press)
KEY operation
Display on 7-Segment
10 times
Inverter compressor 2 check
11 times
Fan 1 check
12 times
Fan 2 check
13 times
End KEY operation
-
f
To use key operating function for service and maintenance when installing module/group, set as main control or
cancel in module/group.
f
During Discharging mode, voltage of Inv1 and Inv2 will be displayed alternately.
f
Even when the power is off, it is dangerous when you come in contact with inverter PCB, fan PCB since high
pressure DC voltage is charged to those parts.
f
When replacing or repairing the PCB, cut-off the power and wait until the DC voltage is discharged before
replacing/repairing them.
- Wait for more than 15 minutes to allow those parts to be fully discharged.
f
When there is error, Discharge mode of DC link voltage may not have been effective. Especially when E464 and
E364 error is displayed, power element might be damaged so do not use the Discharge mode of DC link voltage.
K3 (number of
press)
KEY operation
Display on 7-Segment
1 time
Intialize (Reset) operation
Same as initial state
K4 (number of
press)
Display contents
Display
SEG1
SEG2, 3, 4
1 time
Capacity depending on horsepower
1
AG042K
TTT
0, 1, 5
AG056K
TTT
0, 2, 0
AG070K
TTT
0, 2, 5
2 times
Order frequency (Compressor 1)
2
120 Hz
1, 2, 0
3 times
Order frequency (Compressor 2)
3
120 Hz
1, 2, 0
4 times
High pressure (MPa)
4
1.52 MPa
1, 5, 2
5 times
Low pressure (MPa)
5
0.43 MPa
0, 4, 3
6 times
Discharge temperature (Compressor 1)
6
87 °C
0, 8, 7
7 times
Discharge temperature (Compressor 2)
7
87 °C
0, 8, 7
8 times
IPM temperature (Compressor 1)
8
87 °C
0, 8, 7
9 times
IPM temperature (Compressor 2)
9
87 °C
0, 8, 7
10 times
CT sensor value (Compressor 1)
A
2 A
0, 2, 0
11 times
CT sensor value (Compressor 2)
B
2 A
0, 2, 0
12 times
Suction 1 temperature
C
-42 °C
-, 4, 2
13 times
COND Out temperature
D
-42 °C
-, 4, 2
14 times
Temperature of liquid pipe
E
-42 °C
-, 4, 2
15 times
TOP temperature (Compressor 1)
F
-42 °C
-, 4, 2
16 times
TOP temperature (Compressor 2)
G
-42 °C
-, 4, 2
17 times
Outdoor temperature
H
-42 °C
-, 4, 2
18 times
EVI inlet temperature
I
-42 °C
-, 4, 2