Setting key function
56
English
Installing and setting the option with tact switch and functions
1
Press and hold K2 for 3 seconds. (Only available when the operation is stopped)
f
The display will show the following.
f
If you have set the Emergency operation for compressor malfunction, 1 or 2 will be displayed on Seg 4.
- Seg 1 and Seg 2 will display the number for selected option.
- Seg 3 and Seg 4 will display the number for set value of the selected option.
2
If you have entered option setting, you can shortly press the K1 switch to change the value of the Seg 1 and Seg 2
to select desired option.
f
Refer to the table for the Seg number of the function for each option.
3
If you have selected desired option, you can shortly press the K2 switch to change the value of the Seg 3 and Seg
4 to change the functional setting for the selected option.
f
Refer to the table for the Seg number of the function for each option.
4
After selecting the function for options, press and hold the K2 switch for 2 seconds. Entire 7-segment will blink to
begin tracking mode and value of the option will be be saved. If you do not end the setting mode properly, option
will not be saved.
option item
Input unit
SEG1
SEG2
SEG3
SEG4
Function of the option
Remarks
Emergency
operation for
compressor
malfunction
Individual
0
0
0
0
Disabled
E560 will occur when all
the compressors are set as
malfunction state.
0
1
Set compressor 1 as
malfunction state
0
2
Set compressor 2 as
malfunction state
Unused option
Main
0
1
0
0
Unused option
Unused option
Main
0
2
0
0
Unused option
Unused option
Individual
0
3
0
0
Unused option
oil collection
interval
Main
0
4
0
0
Factory default
0
1
Shorten the interval by 1/2
temperature to
trigger defrost
operation
Main
0
5
0
0
Factory default
0
1
Apply setting when the
product is being installed in
humid area such as near river
or lake