Parameters of the PID Function Block
ACK_OPTION
S
Index: 46
Access:
r, w
Option:
Default:
This parameter allows you to choose whether an alarm should be automatically
acknowledged in the device, i.e. without any influence from the fieldbus host system.
Undefined No
option
HI_HI_ALM
High high alarm
HI_ALM High
alarm
LO_LO_ALM Low
low
alarm
LO_ALM Low
alarm
DV_HI_ALM
Limit alarm for upper range deviation
DV_LO_ALM
Limit alarm for lower range deviation
BLOCK ALM
Block alarm
Undefined
Note:
The alarm is sent to the fieldbus host system, but not acknowledged by it.
ALARM_HYS
S
Index: 47
Access:
r, w
Input:
Default:
Used to input the hysteresis for the high and low alarm limits.
The alarm conditions remain active as long as the measured value is within the
hysteresis. The hysteresis value has an effect on the following alarm limits of the PID
Function Block:
HI_HI_LIM
HI_LIM
LO_LO_LIM
LO_LIM
DV_HI_LIM
DV_LO_LIM
0...50 %
0.5 %
Note: The hysteresis value in percent applies to the range of the PV_SCALE parameter
group in the PID Function Block.
ALARM_SUM
S + D
Index: 45
Access:
r, w
Display:
Shows the current status of process alarms in the PID Function Block
HI_HI_ALM
Violation of the high high alarm
HI_ALM
Violation of the high alarm
LO_LO_ALM
Violation of the low low alarm
LO_ALM
Violation of the low alarm
DV_HI_ALM
Violation of the limit alarm for the upper range deviation
DV_LO_ALM
Violation of the limit alarm for the lower range deviation
BLOCK ALM
Block alarm
Note: Additionally, the process alarm can be cleared in this parameter group.
EB 8383-1 EN
67
Parameter description
Summary of Contents for foundation 3787
Page 83: ...EB 8383 1 EN 83...
Page 84: ...84 EB 8383 1 EN...
Page 85: ...EB 8383 1 EN 85...
Page 86: ...86 EB 8383 1 EN...
Page 87: ...EB 8383 1 EN 87...
Page 88: ...88 EB 8383 1 EN...
Page 89: ...EB 8383 1 EN 89...
Page 90: ...90 EB 8383 1 EN...
Page 91: ...EB 8383 1 EN 91...
Page 92: ...92 EB 8383 1 EN...
Page 93: ...EB 8383 1 EN 93...
Page 94: ...94 EB 8383 1 EN...
Page 95: ...EB 8383 1 EN 95...