Limit switches
For operation of the limit switches, switch-
ing amplifiers have to be connected in the
output circuit. Their function is to control the
limit values of the control circuit according
to NAMUR, thus ensuring operational relia-
bility of the positioner.
If the positioner is installed in hazardous
areas, the relevant regulations must be ob-
served.
Binary input
A passive floating contact can be used at
the binary input. The positioner signals the
status over the bus protocol.
Forced venting
For the positioners with forced venting func-
tion, a voltage between 6 and 24 V DC
must be connected to the terminals 81 and
82.
Note!
If there is no voltage connected or the volt-
age drops, the positioner vents the actuator
and does not respond to the reference vari-
able.
Fig. 9
⋅
Bus line connection and terminal assignment (terminal markings according to DIN 45140)
Brass screw fitting Shield Clamping insert Coupling nut
GW2
GW1
PE
S
NC
-52
+51 -42
+41
-86
+85
-82
+81
EN 61158-2
FOUNDATION
TM
Fieldbus
Bus cable
Switching amplifier
acc. to EN 60 947-5-6
6 to 24 VDC
Limit switches Binary input Forced venting
EB 8383-1 EN
27
Connections
Summary of Contents for foundation 3787
Page 83: ...EB 8383 1 EN 83...
Page 84: ...84 EB 8383 1 EN...
Page 85: ...EB 8383 1 EN 85...
Page 86: ...86 EB 8383 1 EN...
Page 87: ...EB 8383 1 EN 87...
Page 88: ...88 EB 8383 1 EN...
Page 89: ...EB 8383 1 EN 89...
Page 90: ...90 EB 8383 1 EN...
Page 91: ...EB 8383 1 EN 91...
Page 92: ...92 EB 8383 1 EN...
Page 93: ...EB 8383 1 EN 93...
Page 94: ...94 EB 8383 1 EN...
Page 95: ...EB 8383 1 EN 95...