Firmware modifications
Communication
K1.00
K1.20
Version compatible with user interface software version number:
Fisher-Rosemount DeltaV in version 5.1 or higher
National Instruments Fieldbus Configurator in version 2.3 or
higher.
All host systems certified by the Fieldbus Foundation
Alteration to default values of the following parameters:
AO Function Block CHANNEL, PID Function Block GAIN,
PID Function Block RESET, PID Function Block BYPASS
Resource Block parameter extended:
BLOCK_ERROR, page 40
Transducer Block parameters changed/extended:
BLOCK_ERR, page 46.
Communication
K 1.00
K1.31
The output parameters of the function blocks can be
interconnected within a device and with blocks in other devices at
the same time. In the previous version, it was only possible to
either interconnect function blocks within a device or with blocks
in other devices.
An Output Failure in BLOCK_ERR of the AO Function Block
generates a Block Alarm.
The automatic resetting control loop monitor (previously not
automatic resetting) is evaluated for the control loop error
indication via LED or the message "Calibration Error". This means
this alarm or message is automatically reset as soon as the control
loop monitor cannot find an error anymore.
Communication
K 1.31
K1.40
The default value for RESET in the PID Block has been changed
from 0 to 3402823466 x 10
38
(maximum possible value). The
integral-action component of the PID is ineffective at this value as
well as at 0. On switching over the operating mode from MAN to
AUTO, a smooth switchover is achieved.
EB 8383-1 EN
5
Summary of Contents for foundation 3787
Page 83: ...EB 8383 1 EN 83...
Page 84: ...84 EB 8383 1 EN...
Page 85: ...EB 8383 1 EN 85...
Page 86: ...86 EB 8383 1 EN...
Page 87: ...EB 8383 1 EN 87...
Page 88: ...88 EB 8383 1 EN...
Page 89: ...EB 8383 1 EN 89...
Page 90: ...90 EB 8383 1 EN...
Page 91: ...EB 8383 1 EN 91...
Page 92: ...92 EB 8383 1 EN...
Page 93: ...EB 8383 1 EN 93...
Page 94: ...94 EB 8383 1 EN...
Page 95: ...EB 8383 1 EN 95...