STRATEGY
S
Index: 3
Access:
r, w
Default:
The strategy field can be used to identify grouping of blocks to allow a faster analysis
of the blocks. Enter the same number in the STRATEGY parameter of each block to
group blocks.
0
Note: This data is not checked or processed by the Transducer Block.
ST_REV
N
Index: 1
Access:
r
Shows the revision level of the static data.
Note: The revision level will be incremented each time a static parameter in the block is
changed.
TAG_DESC
S
Index: 2
Access:
r, w
Default:
For entering a user-specific text of max. 32 characters to clearly identify and assign
the block.
No text
TOL_OVERSHOOT
S
Index: 36
Access:
r, w
Range:
Default:
Tolerated overshoot
0.1...10 %
0.5 %
TOLERANCE_BAND
S
Index: 38
Access:
r, w
Range:
Default:
Tolerance band
Reset criteria for running control loop monitoring.
Enter the system deviation allowed for it. See also DELAY_TIME.
0.1...10 %
5 %
TOTAL_VALVE_TRAVEL
S
Index: 39
Access:
r
Total valve travel
Sum of the rated load cycles (double travels), sum of valve travels.
TOT_VALVE_TRAV_LIM
S
Index: 40
Access:
r, w
Range:
Default:
Total valve travel limit
0...16 500 000
1 000 000
TRANSDUCER_DIRECTORY
Index: 9
Access:
r
Note:
This parameter is not processed in the Type 3787.
EB 8383-1 EN
53
Parameter description
Summary of Contents for foundation 3787
Page 83: ...EB 8383 1 EN 83...
Page 84: ...84 EB 8383 1 EN...
Page 85: ...EB 8383 1 EN 85...
Page 86: ...86 EB 8383 1 EN...
Page 87: ...EB 8383 1 EN 87...
Page 88: ...88 EB 8383 1 EN...
Page 89: ...EB 8383 1 EN 89...
Page 90: ...90 EB 8383 1 EN...
Page 91: ...EB 8383 1 EN 91...
Page 92: ...92 EB 8383 1 EN...
Page 93: ...EB 8383 1 EN 93...
Page 94: ...94 EB 8383 1 EN...
Page 95: ...EB 8383 1 EN 95...