48
EB 8111/8112 EN
Decommissioning and disassembly
9 Decommissioning and disas-
sembly
Risk of bursting in pressure equipment.
Control valves and pipelines are pressure
equipment. Improper opening can lead to
bursting of the valve.
−
Before starting any work on the control
valve, depressurize all plant sections con
-
cerned and the valve.
−
Drain the process medium from all the
plant sections concerned as well as the
valve.
−
Wear personal protective equipment.
Risk of electric shock.
−
Do not remove any covers to perform ad
-
justment work on live parts.
−
Before performing any work on the device
and before opening the device, disconnect
the power supply and protect it against un-
intentional reconnection.
−
Only use power interruption devices that
are protected against unintentional recon-
nection of the power supply.
Risk of personal injury due to residual pro
-
cess medium in the valve.
While working on the valve, residual process
medium can escape and, depending on its
properties, may lead to personal injury, e.g.
(chemical) burns.
Wear protective clothing, gloves, and eye
-
wear.
Risk of burn injuries due to hot or cold com
-
ponents and pipeline.
Valve components and the pipeline may be-
come very hot or cold. Risk of burn injuries.
−
Allow components and pipelines to cool
down or heat up.
−
Wear protective clothing and gloves.
9.1 Decommissioning
To decommission the control valve for service
and repair work or disassembly, proceed as
follows:
1. Close the shut-off valves upstream and
downstream of the control valve to stop
the process medium from flowing
through the valve.
2. Completely drain the pipelines and
valve.
3. Disconnect and lock the pneumatic air
supply or power supply to depressurize
or de-energize the actuator.
4. If necessary, allow the pipeline and valve
components to cool down or heat up.
9.2 Removing the valve from
the pipeline
1. Put the control valve out of operation (see
section 9.1).
2. Unbolt the flange joint.
DANGER
!
DANGER
!
WARNING
!
WARNING
!
Summary of Contents for 3321
Page 11: ...EB 8111 8112 EN 11 Safety instructions and measures...
Page 27: ...EB 8111 8112 EN 27 Measures...
Page 33: ...EB 8111 8112 EN 33 Mounting and start up...
Page 35: ...EB 8111 8112 EN 35 Operation...
Page 45: ...EB 8111 8112 EN 45 Servicing...
Page 53: ...EB 8111 8112 EN 53...
Page 55: ...EB 8111 8112 EN 55 15 11 12 16 2 5 1 4 13 17 14 63 62 5 2 8 Type 3321 DN 65 to 100 NPS 2 to 4...