SAMLEX AMERICA INC. | 77
SECTION 4 |
Parameter Setup
4.5 GROUP 2 PARAMETER SET UP: INPUT SETTING
4.5.1 Programming Ranges & Default Values of Programming Parameters under Parameter Group
2 – INPUT SETTING
Table 4.6 gives details of programming ranges & default values of parameters under Parameter Group No.2 - "INPUT SETTING".
Refer to Fig 4.3 under Section 4.1.3.2 for Menu Map for navigating through various parameters under this Group No.2
.
TABLE 4.6 Programming Information for Parameter Group No.2 - INPUT SETTING
(Refer to Menu Map at Fig 4.3, Section 4.1.3.2)
Parameter
Setup
Screen
Nos. for:
EVO
-
1212F
1212F-HW
1224F
1224F-HW
4248SP
(Column 1)
Parameter
Setup
Screen
Nos. for:
EVO-
2212/ 2212E
3012/ 3012E
2224/ 2224E
4024/ 4024E
(Column 2)
Parameter
(Column 3)
Setting range
EVO-1212F
/1212F-HW
(Column
4)
EVO-
2212
(Column
5)
EVO-
3012
(Column
6)
EVO-1224F
/1224F-HW
(Column
7)
EVO-
2224
(Column
8)
EVO-
4024
(Column
9)
EVO-
4248SP
(Column
10)
EVO-
2212E
(Column
11)
EVO-
3012E
(Column
12)
EVO-
2224E
(Column
13)
EVO-
4024E
(Column
14)
1
1
DEFAULT FREQ
See NOTE 1
0=60Hz;
(Default:
60Hz)
0=60Hz; 1=50Hz
(Default: 0=60Hz)
See NOTE 1
0=60Hz;
(Default:
0=60Hz)
0=60Hz; 1=50Hz
(Default: 0=60Hz)
0=50Hz; 1=60Hz
(Default: 0=50Hz)
2
2
GRID MAX
CURRENT
5 – 20A
(Default:
20A)
5 – 40A
(Default:
30A)
5 – 70A
(Default:
30A)
5 – 20A
(Default:
20A)
5 – 40A
(Default:
30A)
5 – 70A
(Default:
30A)
5 – 30A
(Default:
30A)
5 – 20A
(Default:
16A)
5 – 25A
(Default:
16A)
5 – 20A
(Default:
16A)
5 – 35A
(Default:
16A)
-
(See NOTE 2)
3
GEN MAX CURRENT
5 – 40A
(Default:
30A)
5 – 70A
(Default:
30A)
5 – 40A
(Default:
30A)
5 – 70A
(Default:
30A)
5 – 20A
(Default:
16A)
5 – 25A
(Default:
16A)
5 – 20A
(Default:
16A)
5 – 35A
(Default:
16A)
3
4
HIGH CUT OFF
50 – 70Hz
(Default: 65Hz)
50 – 70Hz
(Default: 55Hz)
4
5
HIGH RESET
50 – 70Hz
(Default: 64Hz)
50 – 70Hz
(Default: 54Hz)
5
6
LOW CUT OFF
40 – 60Hz
(Default: 55Hz)
40 – 60Hz
(Default: 45Hz)
6
7
LOW RESET
40 – 60Hz
(56Hz)
40 – 60Hz
(Default: 46Hz)
7
–
(See NOTE 3)
SYNCHRONIZATION
0=Fine
(Default)
1=Coarse
0=Fine
(Default)
1=Coarse
0=Fine
(Default)
1=Coarse
–
(See NOTE 4)
8
SYNC GRID
0=Fine (Default)
1=Coarse
0=Fine (Default)
1=Coarse
0=Fine (Default)
1=Coarse
–
(See NOTE 4)
9
SYNC GEN
1=Coarse (Default)
0=Fine
1=Coarse
(Default)
0=Fine
1=Coarse (Default)
0=Fine
8
10
INPUT OC PROTECT
0=INV mode (Default)
1=Shutdown
9
11
INPUT RECOVERY
0=Buffered (Default)
1=Direct